SM45 Operations

Viewing Alarms and System Status Messages (Status View Mode)

Status View Mode displays alarm and status messages.

The appearance of one of the following display indicators in Main Display Mode indicates the presence of an alarm message.

indicates an urgent alarm

indicates a non-urgent alarm

Details about the other display indicators can be found on page 2-2.

Rules for displaying alarms and system status

Active alarms are always displayed before status messages.

Urgent alarms are always displayed before non-urgent alarms.

Alarms with their urgency set to Disabled are not displayed.

Important note about Rect Comms Lost alarm

If a rectifier is removed, a Rectifier Comms Lost alarm is displayed after 10 seconds. The operator or installer then has the opportunity to clear the alarm immediately to prevent triggering an external alarm device. The alarm must be cleared within the configurable Alarm Recognition Time (default is 10 seconds), otherwise an external alarm is generated.

Rects Comms Lost is remotely displayed as Multiple Rectifier Comms Lost.

To view and clear alarms

1 From Main Display Mode, press the key to enter Status View Mode.

2 Press the key to scroll through the list of alarms.

3 Press the key to clear the alarms. (Only three alarms can be cleared – Rect Comms Lost, Rects Comms Lost and Battery Test Fail.)

4 Press the key to return to Main Display Mode.

For a comprehensive list of alarms (that can be displayed in Status View Mode) see

Appendix A.

To view system status messages

1Press the key to enter Status View Mode.

If there are active alarms, press the key to scroll to the bottom of the alarm list. The control status list is displayed after the last alarm.

2Press the or key to scroll through the list of status messages.

3Press the key to return to Main Display Mode.

5-6

Copyright © 2005-2006 Eaton Corporation. All Rights Reserved.

IPN 997-00012-41D December 2006

 

Page 46