Troubleshooting

Problem

Possible Cause/s

Required Action

SM45 displays

Missing configuration

Download the appropriate

Config Error

 

configuration file into the SM45.

 

 

 

 

Invalid configuration

Contact your local Powerware

 

 

DC product representative.

Incorrect number of cells in a battery string – a result of a mismatch between string voltage and nominal rectifier output voltage.

Check the number of cells in a battery string, nominal voltage of each cell and the nominal voltage of the rectifiers.

SM45 displays ???

Incorrectly configured,

Configure, connect or replace

 

disconnected or failed sensor

sensor.