About the SM45 Front Panel

The Audible Indicator

The SM45 has an onboard audible indicator.

The audible indicator informs you about pressing invalid keys and active alarms as follows:

One beep every 2 seconds - indicates that a non-urgent alarm is active

A continuous sound - indicates that an urgent alarm is active

An urgent alarm always overrides a non-urgent alarm.

To disable the audible indicator (when an alarm is active)

Press any key

At the next active alarm, the audible indicator is automatically enabled again.

Display Time-out

The SM45 has a display time-out function – that is, if no keys are pressed for a predetermined time interval, the SM45 reverts back to the default display (total rectifier current).

The predetermined time interval varies (according to the display mode you are in) as follows:

Edit Mode – no time-out

All other display modes – 2 minutes

Changing the Display Contrast

The display contrast can be adjusted from 0 (lowest contrast) to 63 (highest contrast).

To change the display contrast

1 Press the key to enter Configuration Mode.

2 Press the key to scroll down to Display Contrast.

3 Press the key to enter Edit Mode.

4 Press either the or key to change the display contrast as appropriate. (Contrast changes are immediately visible.)

5 Press the key to save the new value.

6 Press the key to return to Main Display Mode.