Appendix C

Specifications

System AC Input

 

AC Input Voltage Range

APU48 rectifiers: 95 – 275 Vrms (L-N)

 

 

 

 

APR48 rectifiers: 185 – 275 Vrms (L-N)

 

 

 

 

 

 

Rated AC Input Current

 

 

 

@ 120 Vrms with APU48 rectifiers

APS3: 21 A (7 A per AC power cord)

 

 

 

 

APS6: 42 A (7 A per AC power cord)

 

 

 

 

 

 

 

@ 240 Vrms with APU48 rectifiers

APS3: 10.5 A (3.5 A per AC power cord)

 

 

 

 

APS6: 21 A (3.5 A per AC power cord)

 

 

 

 

 

 

 

@ 208-240 Vrms with APR48 rectifiers

APS3: 24 A (8 A per AC power cord)

 

 

 

 

APS6: 48 A (8 A per AC power cord)

 

 

 

 

 

Frequency Range

45-66 Hz

 

 

 

 

 

Maximum Earth Leakage Current

1.5 mA (per Access Power Rectifier)

System DC Output

 

 

 

 

 

 

DC Output Voltage (nominal)

48 V

 

 

 

 

 

DC Output Power (maximum)

 

 

 

 

APS3-058 & APS3-060

2.16 kW (with 3 APU48 rectifiers)

 

 

 

 

4.50 kW (with 3 APR48 rectifiers)

 

 

 

 

 

 

 

 

APS3-059 & APS3-061

1.70 kW (with 3 APU48 rectifiers)

 

 

 

 

3.00 kW (with 3 APR48 rectifiers)

 

 

 

 

 

 

 

 

APS6-058

4.32 kW (with 6 APU48 rectifiers)

 

 

 

 

9.00 kW (with 6 APR48 rectifiers)

 

 

 

 

 

 

 

 

APS6-059

3.40 kW (with 6 APU48 rectifiers)

 

 

 

 

7.10 kW (with 6 APR48 rectifiers)

 

 

 

 

DC Output Voltage Range

43 - 57.5 V

 

 

 

 

Over Voltage Shutdown Trip Point

58 V

Environment

 

 

 

 

 

Ambient Temperature Range (operating)

-10°C to +40°C [+14°F to +104°F]

 

 

 

 

Relative Humidity (operating and storage)

<95% (non condensing)

Copyright © 2005-2006 Eaton Corporation. All Rights Reserved.