Pre-Installation

Warnings

This section contains important warnings relating to:

AC Inputs

Equipment Classification

Batteries (if applicable)

DC Outputs

Rectifiers

Location and Environment

Servicing

EMC Compliance

AC Inputs

Desktop Versions:

Pluggable Type A: Except for 120V input, if APS3-06X power systems are fitted with three rectifiers, then only two AC power cords may be connected to one building branch circuit. The third AC power cord must be connected to a separate building branch circuit. Failure to do so voids all safety approvals.

The maximum earth leakage current of each Access Power Rectifier is 1.5 mA. Ensure that any upstream Residual Current Devices (RCDs) are appropriately rated.

The AC power cords (supplying the power system) must be suitably rated for the environment and AC power distribution system. In addition, these AC power cords must be approved and installed to comply with local wiring regulations.

The earth conductor of each AC power cord must have a minimum cross sectional area of 1 mm2 (0.00155 in2).

The maximum length of each AC power cord should not exceed 3m (10 feet), unless local wiring regulations permit otherwise.

Ensure that the AC supply is disconnected from those fused AC power sockets before checking or replacing their respective fuses.

Each socket, K1 to K3 (APS3), and K1 to K6 (APS6), contain two fuses, FS1 and FS2.

CAUTION: DOUBLE-POLE / NEUTRAL FUSING

Use only 15 A, 250 VAC, 6.3 x 32 mm, fast-acting fuses of the same type (Bussman ABC-15 or Littelfuse 314-015 Type 3AB) for continued protection against risk of fire.

Equipment Classification

Data Power Solutions are classified as “Class 1” equipment that must be provided with an earth connected to the “Protective Earthing Conductor” in the building wiring. The earth conductor of each AC power cord must be connected to the “Protective Earthing Conductor” in the building wiring.

APS3-06X (desktop versions) are classed as “Pluggable equipment Type A” and intended for use as “Desktop units”. All other units, APS3-05X and APS6-05X are “Pluggable Equipment Type B” or for “Permanently connection” in host equipment.

2-2

Copyright © 2005-2006 Eaton Corporation. All Rights Reserved.

IPN 997-00012-41D December 2006

 