Eaton Electrical SC200 manual Data Power Solutions Product Range, General Description

Models: SC200

1 78
Download 78 pages 21.25 Kb
Page 8
Image 8

General Description

Data Power Solutions Product Range

Data Power Solutions provide high reliability 48 V DC power for Power over Ethernet, network, data and telecommunications equipment.

Each power system includes AC/DC rectifier modules, a supervisory module to provide control and communications functions, circuit breakers to protect the output cabling, and output terminals to connect the cables to the DC powered equipment and optional batteries.

Six models (with eight variants each) are available, as shown on the following three pages.

APS3-058-xrack-mounted version, without battery option

APS3-059-xrack-mounted version, with battery option

APS3-060-x– desktop version, without battery option

APS3-061-x– desktop version, with battery option

APS6-058-xrack-mounted version, without battery option

APS6-059-xrack-mounted version, with battery option

Where “–x” indicates the model variant with the following type and number of circuit breakers:

x

Number of 25A

Number of 6A

 

Circuit

Circuit

 

Breakers

Breakers

 

 

 

0

4

4

 

 

 

1

5

3

 

 

 

2

6

2

 

 

 

3

7

1

 

 

 

4

8

0

 

 

 

5

3

5

 

 

 

6

2

6

 

 

 

7

1

7

 

 

 

8

0

8

 

 

 

AC Input: Data Power Solutions can be powered by a wide range of AC power distribution systems such as single-phase, two-phase, three-phase (L-N) and three-phase (L-L). Depending on the nominal voltage of the AC supply (120 V or 240 V), the power systems are equipped with either APU48 or APR48 rectifiers. Fused AC power sockets (one per rectifier) are available for connecting the power system to the AC supply.

DC Output: Eight floating DC outlets are available for connecting equipment power cables. Each DC outlet is protected by a corresponding 6 A or 25 A load circuit breaker. Any combination of 6 A or 25 A rated load circuit breakers (up to a maximum of eight) can be fitted, depending on customer requirements.

Battery Option: External VRLA 48 V batteries can be connected to APS3-059, APS3-061 and APS6-059 models to provide backup power during AC outages. The battery float voltage is temperature compensated.

1-2

Copyright © 2005-2006 Eaton Corporation. All Rights Reserved.

IPN 997-00012-41D December 2006

 

Page 8
Image 8
Eaton Electrical SC200 manual Data Power Solutions Product Range, General Description