Maintenance

Troubleshooting

Use the table below to troubleshoot minor power system installation and operational problems. If you still cannot solve a problem, contact your local Powerware DC product representative for assistance.

Problem

Possible Cause/s

Required Action

All rectifiers are off

AC power to the system is off

Restore AC power.

(no LEDs on) and

and the batteries are fully

 

SM45 display is blank

discharged or disconnected.

 

 

 

 

Green LED of one or

AC power to rectifier(s) off or

Restore AC power.

more rectifiers is off

one or more phases are off

 

 

 

 

 

Rectifier is not fully inserted.

Check that the rectifier is fully

 

 

inserted.

 

 

 

 

Internal rectifier fault

Remove the rectifier and insert

 

 

another one in the same slot.

 

 

If the second rectifier operates

 

 

normally, the first rectifier is

 

 

faulty and must be returned to

 

 

your local Powerware DC

 

 

product representative.

 

 

 

Rectifier red LED on

Very low AC voltage or AC

Check the AC supply. The

 

supply failed

power system will return to

 

 

normal operation when the AC

 

 

supply has returned to within its

 

 

specified AC input voltage

 

 

range. See Appendix C.

 

 

 

 

AC overvoltage

None. The power system will

 

 

return to normal operation when

 

 

the AC supply has returned to

 

 

within its specified AC input

 

 

voltage range, as specified in

 

 

Appendix C.

 

 

 

 

Rectifier shut down

Check if a rectifier has in fact

 

 

been shut down, using DCTools.

 

 

If yes, turn on the rectifier using

 

 

DCTools.

 

 

 

 

Rectifier(s) failed

Use DCTools to determine if a

 

 

rectifier has failed or has been

 

 

shut down.

 

 

If a rectifier has failed, replace it.

 

 

If a rectifier has been shut down,

 

 

refer to required action for

 

 

Rectifier Shut Down.

 

 

 

 

DC overvoltage

Remove and re-insert rectifier(s)

 

 

after approximately 5 seconds.