Maintenance

Problem

Possible Cause/s

Required Action

SM45 does not correctly register the current shunts and the displayed values are over range.

Local/External current shunt

Contact your local Powewrware

selector switches in the wrong

DC product representative.

position.

 

SM45 display is

Faulty SM45 display or

Contact your local Powewrware

blank.

 

disconnected display loom.

DC product representative.

SM45 green

 

SM45 is not powered

Check the SM45 card is fully

Power On LED off.

 

inserted into the backplane.

 

 

SM45 is faulty.

Contact your local Powerware

 

 

 

DC product representative.

SM45 red

LED on

SM45 “Urgent Alarm” is active.

Check the type of “Urgent

 

 

 

Alarm” using DCTools or press

 

 

 

the

key on the SM45 front

 

 

 

panel.

 

SM45 yellow

LED

SM45 “Non-Urgent Alarm” is

Check the type of “Non-urgent

on

 

active.

Alarm” using DCTools or press

 

 

 

the

key on the SM45 front

 

 

 

panel.

 

No Ethernet

 

Wrong IP address, netmask

Check the settings with the

communications

and/or incompatible network

network administrator.

between SM45 and

Gateway may be required

 

 

local PC

 

 

 

 

Faulty communications cable

Replace faulty cable.

 

 

 

 

The Telnet Active check box in

Disable the Telnet Active check

 

 

the DCTools Comms Properties

box in the DCTools Comms

 

 

dialog is enabled.

Properties dialog.

No communications

Incorrect cable

Check that a null modem cable

between SM45 and

 

has been used.

local PC

 

Null modem cable not plugged

Check that the null modem

 

 

 

 

into PC or plugged into the

cable is plugged into the PC and

 

 

wrong port.

into the correct port.

 

 

Communications port settings

Reconfigure the PC port

 

 

of PC do not match that of the

properties (19K2 8 N 1).

 

 

RS-232 serial port of the power

 

 

 

 

system.

 

 

 

 

Incorrect S3P address.

Check that the S3P address in

 

 

 

DCTools is set to 0.

continued

7-4

Copyright © 2005-2006 Eaton Corporation. All Rights Reserved.

IPN 997-00012-41D December 2006

 