Installing the hardware
Installation requirements for AC redundant configurations
The AC redundant configuration is with two PSUs plugged into a main AC source and two other PSUs plugged into a separate AC source (e.g. UPS).
PSU configuration | Max. DC loading | DC redundancy |
2 + 1 | 4800 W | Yes |
|
|
|
2 + 2 | 6400 W | Yes |
|
|
|
Table 2: Maximum DC loading requirements
Installation requirements for non AC redundant configurations
For systems not requiring AC redundancy, the power supply can be installed with up to 4 PSUs. The PSUs can be connected to a single or multiple AC sources.
PSU configuration | Max. DC loading | DC redundancy |
|
|
|
2 | 3200 W | No |
|
|
|
2 + 1 | 4800 W | Yes |
|
|
|
2 + 2 | 6400 W | Yes |
|
|
|
Table 3: Maximum DC loading requirements
52 | Operating Manual | BX400 S1 |