489

Communications Guide

Modbus Functions

Function Code 07: Read Device Status

Function Code 08: Loopback Test

Modbus Implementation: Read Exception Status

489 Implementation: Read Device Status

This function reads the selected device status. A short message length allows for rapid reading of status. The returned status byte has individual bits set to 1 or 0 depending on the slave device status. The 489 general status byte is shown below:

BIT

DESCRIPTION

 

BIT

DESCRIPTION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B0

1

TRIP relay operated = 1

 

B4

5

ALARM relay operated = 1

 

 

 

 

 

 

 

B1

2

AUXILIARY relay operated = 1

 

B5

6

SERVICE relay operated = 1

 

 

 

 

 

 

B2

3

AUXILIARY relay operated = 1

 

B6

Stopped = 1

 

 

 

 

 

 

B3

4

AUXILIARY relay operated = 1

 

B7

Running = 1

 

 

 

 

 

 

 

Note that if status is neither stopped or running, the generator is starting.

Message Format and Example:

Request status from slave 11.

Master Transmission

Bytes

Example

Description

 

 

 

 

 

 

 

 

Slave Address

1

0B

message for slave 11

 

 

 

 

Function Code

1

07

read device status

 

 

 

 

CRC (low, high)

2

47 42

computed CRC error code

 

 

 

 

Slave Response

Bytes

Example

Description

 

 

 

 

 

 

 

 

Slave Address

1

0B

message from slave 11

 

 

 

 

Function Code

1

07

read device status

 

 

 

 

Device Status

1

59

status = 01011001b

 

 

 

 

CRC (low, high)

2

C2 08

computed CRC error code

 

 

 

 

Modbus Implementation: Loopback Test

489 Implementation: Loopback Test

This function is used to test the integrity of the communication link. The 489 will echo the request.

Message Format and Example:

Loopback test from slave 11.

Master Transmission

Bytes

Example

Description

 

 

 

 

Slave Address

1

0B

message for slave 11

 

 

 

 

Function Code

1

08

loopback test

 

 

 

 

Diagnostic Code

2

00 00

must be 0000h

 

 

 

 

Data

2

00 00

must be 0000h

 

 

 

 

CRC (low, high)

2

E0 A1

computed CRC error code

 

 

 

 

Slave Response

Bytes

Example

Description

 

 

 

 

Slave Address

1

0B

message from slave 11

 

 

 

 

Function Code

1

08

loopback test

 

 

 

 

Diagnostic Code

2

00 00

must be 0000h

 

 

 

 

Data

2

00 00

must be 0000h

 

 

 

 

CRC (low, high)

2

E0 A1

computed CRC error code

 

 

 

 