DNP Point Lists

Analog Input / Input Change (Objects 30/32)

489

Communications Guide

In the following table, the Format column indicates that the associated data point format is determined by the entry in Data Formats on page 40. For example, an “F1” format is described in that table as a (16-bit) unsigned value without any decimal places. Therefore, the value read should be interpreted in this manner. Many of the values reported by the 489 have a size of 32-bits and have had their upper and lower 16-bit components assigned to separate points. Where indicated, refer to the appropriate note following the table for more detail.

Table 8: Analog Inputs Point List (Sheet 1 of 4)

INDEX

FOR-

DESCRIPTION

EVENT CLASS

NOTES

 

MAT

 

ASSIGNED TO

 

 

 

 

 

 

 

 

 

 

 

0

F133

Generator Status

Class 1

Note 3

 

 

 

 

 

1

F1

Generator Thermal Capacity Used

Class 1

 

 

 

 

 

 

2

F1

Estimated Trip Time On Overload

Class 1

 

 

 

(seconds, 65535 means never)

 

 

 

 

 

 

 

3

F134

Cause Of Last Trip

Class 1

Note 3

 

 

 

 

 

4

F19

Time Of Last Trip (Upper 16 Bits)

Class 1

Notes 3,4

 

 

 

 

 

5

F19

Time Of Last Trip (Lower 16 Bits)

Class 1

Notes 3,4

 

 

 

 

 

6

F18

Date Of Last Trip (Upper 16 Bits)

Class 1

Notes 3,4

 

 

 

 

 

7

F18

Date Of Last Trip (Lower 16 Bits)

Class 1

Notes 3,4

 

 

 

 

 

8

F1

Tachometer Pre-Trip

Class 1

Note 3

 

 

 

 

 

9

F1

Scale factor for pre-trip current readings

Class 1

Note 3

 

 

(pre-trip points marked with “Note 6”).

 

 

 

 

Will always be a power of 10 (1, 10, 100,

 

 

 

 

etc.). Changes only when the configuration

 

 

 

 

setpoints are changed.

 

 

 

 

 

 

 

10

F1

Phase A Pre-Trip Current

Class 1

Notes 3, 6

 

 

 

 

 

11

F1

Phase B Pre-Trip Current

Class 1

Notes 3, 6

 

 

 

 

 

12

F1

Phase C Pre-Trip Current

Class 1

Notes 3, 6

 

 

 

 

 

13

F1

Phase A Pre-Trip Differential Current

Class 1

Notes 3, 6

 

 

 

 

 

14

F1

Phase B Pre-Trip Differential Current

Class 1

Notes 3, 6

 

 

 

 

 

15

F1

Phase C Pre-Trip Differential Current

Class 1

Notes 3, 6

 

 

 

 

 

16

F1

Pre-Trip Negative Sequence Current

Class 1

Note 3

 

 

 

 

 

17

F1

Ground Current Scale Factor. Will always

Class 1

Note 3

 

 

be a power of 10 (1, 10, 100, etc.).

 

 

 

 

Changes only when the configuration

 

 

 

 

setpoints are changed.

 

 

 

 

 

 

 

18

F6

Pre-Trip Ground Current (scaled according

Class 1

Note 3

 

 

to previous setpoint)

 

 

 

 

 

 

 

19

F1

Phase A-B Pre-Trip Voltage

Class 1

Note 3

 

 

 

 

 

20

F1

Phase B-C Pre-Trip Voltage

Class 1

Note 3

 

 

 

 

 

21

F1

Phase C-A Pre-Trip Voltage

Class 1

Note 3

 

 

 

 

 

22

F3

Pre-Trip Frequency

Class 1

Note 3

 

 

 

 

 

23

F1

Pre-Trip Real Power (MW)

Class 1

Notes 3,8

 

 

 

 

 

24

F1

Pre-Trip Real Power (kW)

Class 1

Notes 3,8

 

 

 

 

 

25

F1

Pre-Trip Reactive Power (Mar

Class 1

Notes 3,8

 

 

 

 

 

26

F1

Pre-Trip Reactive Power (kvar)

Class 1

Notes 3,8

 

 

 

 

 

27

F1

Pre-Trip Apparent Power (MVA)

Class 1

Notes 3,8

 

 

 

 

 

28

F1

Pre-Trip Apparent Power (kVA)

Class 1

Notes 3,8

 

 

 

 

 

29

F1

Last Trip Stator RTD

Class 1

Note 3

 

 

 

 

 

30

F4

Last Trip Hottest Stator RTD Temperature

Class 1

Note 3

 

 

(°C)

 

 

 

 

 

 

 

31

F1

Last Trip Bearing RTD

Class 1

Note 3

 

 

 

 

 

32

F4

Last Trip Hottest Bearing RTD Temperature

Class 1

Note 3

 

 

(°C)

 

 

 

 

 

 

 

33

F1

Last Trip Other RTD

Class 1

Note 3

 

 

 

 

 

34

F4

Last Trip Hottest Other RTD Temperature

Class 1

Note 3

 

 

(°C)

 

 

 

 

 

 

 