Modbus Memory Map

Table 1: 489 Memory Map (Sheet 27 of 29)

489

Communications Guide

ADDR

NAME

RANGE

STEP

UNITS

FORMAT

DEFAULT

 

 

 

 

 

 

 

2C58

Analog Input 2 Trip Pickup

0 to 1

1

F130

0

 

 

 

 

 

 

 

2C59

Analog Input 2 Trip Delay

1 to 3000

1

s

F2

1

 

 

 

 

 

 

 

2C5A

Analog Input 2 Name

0 to 12

1

F22

_

 

 

 

 

 

 

 

ANALOG INPUT/OUTPUT / ANALOG INPUT 3

 

 

 

 

 

 

 

 

 

 

 

 

2C80

Analog Input 3

0 to 3

1

F129

0

 

 

 

 

 

 

 

2C85

Analog Input 3 Units

0 to 6

1

F22

_

 

 

 

 

 

 

 

2C88

Analog Input 3 Minimum

–50000 to 50000

1

Units

F12

0

 

 

 

 

 

 

 

2C8A

Analog Input 3 Maximum

–50000 to 50000

1

Units

F12

100

 

 

 

 

 

 

 

2C8C

Block Analog Input 3 From Online

0 to 5000

1

s

F1

0

 

 

 

 

 

 

 

2C8D

Analog Input 3 Alarm

0 to 2

1

F115

0

 

 

 

 

 

 

 

2C8E

Assign Alarm Relays (2-5)

1 to 4

1

F50

16

 

 

 

 

 

 

 

2C8F

Analog Input 3 Alarm Level

–50000 to 50000

1

Units

F12

10

 

 

 

 

 

 

 

2C91

Analog Input 3 Alarm Pickup

0 to 1

1

F130

0

 

 

 

 

 

 

 

2C92

Analog Input 3 Alarm Delay

1 to 3000

1

s

F2

1

 

 

 

 

 

 

 

2C93

Analog Input 3 Alarm Events

0 to 1

1

F105

0

 

 

 

 

 

 

 

2C94

Analog Input 3 Trip

0 to 2

1

F115

0

 

 

 

 

 

 

 

2C95

Assign Trip Relays (1-4)

0 to 3

1

F50

1

 

 

 

 

 

 

 

2C96

Analog Input 3 Trip Level

–50000 to 50000

1

Units

F12

20

 

 

 

 

 

 

 

2C98

Analog Input 3 Trip Pickup

0 to 1

1

F130

0

 

 

 

 

 

 

 

2C99

Analog Input 3 Trip Delay

1 to 3000

1

s

F2

1

 

 

 

 

 

 

 

2C9A

Analog Input 3 Name

0 to 12

1

F22

_

 

 

 

 

 

 

 

ANALOG INPUT/OUTPUT / ANALOG INPUT 4

 

 

 

 

 

 

 

 

 

 

 

 

2CC0

Analog Input 4

0 to 3

1

F129

0

 

 

 

 

 

 

 

2CC5

Analog Input 4 Units

0 to 6

1

F22

_

 

 

 

 

 

 

 

2CC8

Analog Input 4 Minimum

–50000 to 50000

1

Units

F12

0

 

 

 

 

 

 

 

2CCA

Analog Input 4 Maximum

–50000 to 50000

1

Units

F12

100

 

 

 

 

 

 

 

2CCC

Block Analog Input 4 From Online

0 to 5000

1

s

F1

0

 

 

 

 

 

 

 

2CCD

Analog Input 4 Alarm

0 to 2

1

F115

0

 

 

 

 

 

 

 

2CCE

Assign Alarm Relays (2-5)

1 to 4

1

F50

16

 

 

 

 

 

 

 

2CCF

Analog Input 4 Alarm Level

–50000 to 50000

1

Units

F12

10

 

 

 

 

 

 

 

2CD1

Analog Input 4 Alarm Pickup

0 to 1

1

F130

0

 

 

 

 

 

 

 

2CD2

Analog Input 4 Alarm Delay

1 to 3000

1

s

F2

1

 

 

 

 

 

 

 

2CD3

Analog Input 4 Alarm Events

0 to 1

1

F105

0

 

 

 

 

 

 

 

2CD4

Analog Input 4 Trip

0 to 2

1

F115

0

 

 

 

 

 

 

 

2CD5

Assign Trip Relays (1-4)

0 to 3

1

F50

1

 

 

 

 

 

 

 

2CD6

Analog Input 4 Trip Level

–50000 to 50000

1

Units

F12

20

 

 

 

 

 

 

 

2CD8

Analog Input 4 Trip Pickup

0 to 1

1

F130

0

 

 

 

 

 

 

 

2CD9

Analog Input 4 Trip Delay

1 to 3000

1

s

F2

1

 

 

 

 

 

 

 

2CDA

Analog Input 4 Name

0 to 12

1

F22

_

 

 

 

 

 

 

 

489 TESTING / SIMULATION MODE

 

 

 

 

 

 

 

 

 

 

 

 

2D00

Simulation Mode

0 to 3

1

F138

0

 

 

 

 

 

 

 

2D01

Pre-fault To Fault Time Delay

0 to 300

1

s

F1

15

 

 

 

 

 

 

 

489 TESTING / PRE-FAULT SETUP

 

 

 

 

 

 

 

 

 

 

 

 

2D20

Pre-Fault Iphase Output

0 to 2000

1

CT

F3

0

 

 

 

 

 

 

 

2D21

Pre-Fault Voltages Phase-N

0 to 150

1

Rated

F3

100

 

 

 

 

 

 

 

2D22

Pre-Fault Current Lags Voltage

0 to 359

1

°

F1

0

 

 

 

 

 

 

 

2D23

Pre-Fault Iphase Neutral

0 to 2000

1

CT

F3

0

 

 

 

 

 

 

 

2D24

Pre-Fault Current Ground

0 to 2000

1

CT

F3

0

 

 

 

 

 

 

 

2D25

Pre-Fault Voltage Neutral

0 to 1000

1

Volts

F2

0

 

 

 

 

 

 

 

2D26

Pre-Fault Stator RTD Temp

–50 to 250

1

°C

F4

40

 

 

 

 

 

 

 

2D27

Pre-Fault Bearing RTD Temp

–50 to 250

1

°C

F4

40

 

 

 

 

 

 

 

2D28

Pre-Fault Other RTD Temp

–50 to 250

1

°C

F4

40

 

 

 

 

 

 

 

2D29

Pre-Fault Ambient RTD Temp

–50 to 250

1

°C

F4

40

 

 

 

 

 

 

 

1, 2, 3 See Table footnotes on page 39