 | 489 | 
 | 
 | 
 | 
 | Modbus Memory Map | ||
| 
 | Communications Guide | 
 | 
 | 
 | 
 | 
 | 
 | 
 | |
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 
 | Table 1: 489 Memory Map (Sheet 20 of 29) | 
 | 
 | 
 | 
 | 
 | 
 | ||
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | ||
| 
 | ADDR | NAME | RANGE | STEP | UNITS | FORMAT | DEFAULT | ||
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | |
| 
 | 2428 | RTD #1 Trip Temperature | 1 to 250 | 1 | °C | F1 | 155 | 
 | |
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | |
| 
 | 2429 | RTD #1 Name | 0 to 8 | 1 | – | F22 | _ | 
 | |
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | |
| 
 | RTD TEMPERATURE / RTD #2 | 
 | 
 | 
 | 
 | 
 | 
 | ||
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | |
| 
 | 2460 | RTD #2 Application | 0 to 4 | 1 | – | F121 | 1 | 
 | |
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | |
| 
 | 2461 | RTD #2 Alarm | 0 to 2 | 1 | – | F115 | 0 | 
 | |
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | |
| 
 | 2462 | Assign Alarm Relays  | 1 to 4 | 1 | – | F50 | 16 | 
 | |
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | |
| 
 | 2463 | RTD #2 Alarm Temperature | 1 to 250 | 1 | °C | F1 | 130 | 
 | |
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | |
| 
 | 2464 | RTD #2 Alarm Events | 0 to 1 | 1 | – | F105 | 0 | 
 | |
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | |
| 
 | 2465 | RTD #2 Trip | 0 to 2 | 1 | – | F115 | 0 | 
 | |
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | |
| 
 | 2466 | RTD #2 Trip Voting | 1 to 12 | 1 | – | F122 | 2 | 
 | |
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | |
| 
 | 2467 | Assign Trip Relays  | 0 to 3 | 1 | – | F50 | 1 | 
 | |
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | |
| 
 | 2468 | RTD #2 Trip Temperature | 1 to 250 | 1 | °C | F1 | 155 | 
 | |
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | |
| 
 | 2469 | RTD #2 Name | 0 to 8 | 1 | – | F22 | _ | 
 | |
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | |
| 
 | RTD TEMPERATURE / RTD #3 | 
 | 
 | 
 | 
 | 
 | 
 | ||
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | |
| 
 | 24A0 | RTD #3 Application | 0 to 4 | 1 | – | F121 | 1 | 
 | |
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | |
| 
 | 24A1 | RTD #3 Alarm | 0 to 2 | 1 | – | F115 | 0 | 
 | |
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | |
| 
 | 24A2 | Assign Alarm Relays  | 1 to 4 | 1 | – | F50 | 16 | 
 | |
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | |
| 
 | 24A3 | RTD #3 Alarm Temperature | 1 to 250 | 1 | °C | F1 | 130 | 
 | |
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | |
| 
 | 24A4 | RTD #3 Alarm Events | 0 to 1 | 1 | – | F105 | 0 | 
 | |
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | |
| 
 | 24A5 | RTD #3 Trip | 0 to 2 | 1 | – | F115 | 0 | 
 | |
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | |
| 
 | 24A6 | RTD #3 Trip Voting | 1 to 12 | 1 | – | F122 | 3 | 
 | |
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | |
| 
 | 24A7 | Assign Trip Relays  | 0 to 3 | 1 | – | F50 | 1 | 
 | |
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | |
| 
 | 24A8 | RTD #3 Trip Temperature | 1 to 250 | 1 | °C | F1 | 155 | 
 | |
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | |
| 
 | 24A9 | RTD #3 Name | 0 to 8 | 1 | – | F22 | _ | 
 | |
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | |
| 
 | RTD TEMPERATURE / RTD #4 | 
 | 
 | 
 | 
 | 
 | 
 | ||
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | |
| 
 | 24E0 | RTD #4 Application | 0 to 4 | 1 | – | F121 | 1 | 
 | |
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | |
| 
 | 24E1 | RTD #4 Alarm | 0 to 2 | 1 | – | F115 | 0 | 
 | |
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | |
| 
 | 24E2 | Assign Alarm Relays  | 1 to 4 | 1 | – | F50 | 16 | 
 | |
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | |
| 
 | 24E3 | RTD #4 Alarm Temperature | 1 to 250 | 1 | °C | F1 | 130 | 
 | |
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | |
| 
 | 24E4 | RTD #4 Alarm Events | 0 to 1 | 1 | – | F105 | 0 | 
 | |
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | |
| 
 | 24E5 | RTD #4 Trip | 0 to 2 | 1 | – | F115 | 0 | 
 | |
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | |
| 
 | 24E6 | RTD #4 Trip Voting | 1 to 12 | 1 | – | F122 | 4 | 
 | |
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | |
| 
 | 24E7 | Assign Trip Relays  | 0 to 3 | 1 | – | F50 | 1 | 
 | |
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | |
| 
 | 24E8 | RTD #4 Trip Temperature | 1 to 250 | 1 | °C | F1 | 155 | 
 | |
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | |
| 
 | 24E9 | RTD #4 Name | 0 to 8 | 1 | – | F22 | _ | 
 | |
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | |
| 
 | RTD TEMPERATURE / RTD #5 | 
 | 
 | 
 | 
 | 
 | 
 | ||
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | |
| 
 | 2520 | RTD #5 Application | 0 to 4 | 1 | – | F121 | 1 | 
 | |
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | |
| 
 | 2521 | RTD #5 Alarm | 0 to 2 | 1 | – | F115 | 0 | 
 | |
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | |
| 
 | 2522 | Assign Alarm Relays  | 1 to 4 | 1 | – | F50 | 16 | 
 | |
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | |
| 
 | 2523 | RTD #5 Alarm Temperature | 1 to 250 | 1 | °C | F1 | 130 | 
 | |
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | |
| 
 | 2524 | RTD #5 Alarm Events | 0 to 1 | 1 | – | F105 | 0 | 
 | |
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | |
| 
 | 2525 | RTD #5 Trip | 0 to 2 | 1 | – | F115 | 0 | 
 | |
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | |
| 
 | 2526 | RTD #5 Trip Voting | 1 to 12 | 1 | – | F122 | 5 | 
 | |
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | |
| 
 | 2527 | Assign Trip Relays  | 0 to 3 | 1 | – | F50 | 1 | 
 | |
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | |
| 
 | 2528 | RTD #5 Trip Temperature | 1 to 250 | 1 | °C | F1 | 155 | 
 | |
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | |
| 
 | 2529 | RTD #5 Name | 0 to 8 | 1 | – | F22 | _ | 
 | |
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | |
| 
 | RTD TEMPERATURE / RTD #6 | 
 | 
 | 
 | 
 | 
 | 
 | ||
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | |
| 
 | 2560 | RTD #6 Application | 0 to 4 | 1 | – | F121 | 1 | 
 | |
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | |
| 
 | 2561 | RTD #6 Alarm | 0 to 2 | 1 | – | F115 | 0 | 
 | |
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | |
| 
 | 2562 | Assign Alarm Relays  | 1 to 4 | 1 | – | F50 | 16 | 
 | |
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | |
| 
 | 2563 | RTD #6 Alarm Temperature | 1 to 250 | 1 | °C | F1 | 130 | 
 | |
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | |
| 
 | 2564 | RTD #6 Alarm Events | 0 to 1 | 1 | – | F105 | 0 | 
 | |
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | |
| 
 | 2565 | RTD #6 Trip | 0 to 2 | 1 | – | F115 | 0 | 
 | |
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
1, 2, 3 See Table footnotes on page 39
| 30 | 
http://www.GEindustrial.com/multilin
| GE Multilin | 