 | 489 | 
 | 
 | 
 | 
 | Modbus Memory Map | ||
| 
 | Communications Guide | 
 | 
 | 
 | 
 | 
 | 
 | 
 | ||
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | |
| 
 | Table 1: 489 Memory Map (Sheet 8 of 29) | 
 | 
 | 
 | 
 | 
 | 
 | |||
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | |
| 
 | ADDR | NAME | 
 | 
 | RANGE | STEP | UNITS | FORMAT | DEFAULT | |
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | ||
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | ||
| 
 | 07A1 | Number Of Thermal Resets | 0 to 50000 | 1 | – | F1 | 0 | 
 | ||
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | ||
| 
 | MAINTENANCE / TRIP COUNTERS | 
 | 
 | 
 | 
 | 
 | 
 | |||
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | |
| 
 | 07A2 | Loss Of Excitation 1 | Trips | 0 to 50000 | 1 | – | F1 | 0 | 
 | |
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | |
| 
 | 07A3 | Loss Of Excitation 2 | Trips | 0 to 50000 | 1 | – | F1 | 0 | 
 | |
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | ||
| 
 | 07A4 | Ground Directional Trips | 0 to 50000 | 1 | – | F1 | 0 | 
 | ||
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | ||
| 
 | 07A5 | 0 to 50000 | 1 | – | F1 | 0 | 
 | |||
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | ||
| 
 | 07A6 | Distance Zone 1 Trips | 0 to 50000 | 1 | – | F1 | 0 | 
 | ||
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | ||
| 
 | 07A7 | Distance Zone 2 Trips | 0 to 50000 | 1 | – | F1 | 0 | 
 | ||
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 
 | MAINTENANCE / TIMERS | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | |
07E0 Generator Hours Online
0 to 1000000
1
h
F12
0
PRODUCT INFO. / 489 MODEL INFO.
| 0800 | Order Code | 0 to 65535 | 1 | N/A | F136 | N/A | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 0801 | 489 Serial Number | 3000000 to 9999999 | 1 | – | F12 | 3000000 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| PRODUCT INFO. / CALIBRATION INFO. | 
 | 
 | 
 | 
 | 
 | |
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 0810 | Original Calibration Date | N/A | N/A | N/A | F18 | N/A | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 0812 | Last Calibration Date | N/A | N/A | N/A | F18 | N/A | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 489 SETUP / PREFERENCES | 
 | 
 | 
 | 
 | 
 | |
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 1000 | Default Message Cycle Time | 5 to 100 | 5 | s | F2 | 20 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 1001 | Default Message Timeout | 10 to 900 | 1 | s | F1 | 300 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 1003 | Parameter Averages Calculation Period | 1 to 90 | 1 | min | F1 | 15 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 1004 | Temperature Display | 0 to 1 | 1 | – | F100 | 0 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 1005 | Waveform Trigger Position | 1 to 100 | 1 | % | F1 | 25 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 1006 | Passcode (Write Only) | 0 to 99999999 | 1 | N/A | F12 | 0 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 1008 | Encrypted Passcode (Read Only) | N/A | N/A | N/A | F12 | N/A | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 100A | Waveform Memory Buffer | 1 to 16 | 1 | – | F1 | 8 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 489 SETUP / SERIAL PORTS | 
 | 
 | 
 | 
 | 
 | |
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 1010 | Slave Address | 1 to 254 | 1 | – | F1 | 254 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 1011 | Computer RS485 Baud Rate | 0 to 5 | 1 | – | F101 | 4 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 1012 | Computer RS485 Parity | 0 to 2 | 1 | – | F102 | 0 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 1013 | Auxiliary RS485 Baud Rate | 0 to 5 | 1 | – | F101 | 4 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 1014 | Auxiliary RS485 Parity | 0 to 2 | 1 | – | F102 | 0 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 1015 | Port Used For DNP | 0 to 3 | 1 | – | F216 | 0 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 1016 | DNP Slave Address | 0 to 255 | 1 | – | F1 | 255 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 1017 | DNP Turnaround Time | 0 to 100 | 10 | ms | F1 | 10 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
489 SETUP / REAL TIME CLOCK
| 1030 | Date | 
| 1032 | Time | 
| 1034 | |
| 
 | 
 | 
| N/A | N/A | N/A | F18 | N/A | 
| N/A | N/A | N/A | F19 | N/A | 
| 0 to 2 | 1 | – | F220 | 0 | 
| 
 | 
 | 
 | 
 | 
 | 
489 SETUP / MESSAGE SCRATCHPAD
1060 Scratchpad
1080 Scratchpad
10A0 Scratchpad
10C0 Scratchpad
10E0 Scratchpad
| 0 to 40 | 1 | – | F22 | _ | 
| 0 to 40 | 1 | – | F22 | _ | 
| 0 to 40 | 1 | – | F22 | _ | 
| 0 to 40 | 1 | – | F22 | _ | 
| 0 to 40 | 1 | – | F22 | _ | 
| 
 | 
 | 
 | 
 | 
 | 
489 SETUP / CLEAR DATA
| 1130 | Clear Last Trip Data | 0 to 1 | 1 | – | F103 | 0 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 1131 | Clear Mwh And Mvarh Meters | 0 to 1 | 1 | – | F103 | 0 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 1132 | Clear Peak Demand Data | 0 to 1 | 1 | – | F103 | 0 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 1133 | Clear RTD Maximums | 0 to 1 | 1 | – | F103 | 0 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 1134 | Clear Analog Inputs Minimums/Maximums | 0 to 1 | 1 | – | F103 | 0 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 1135 | Clear Trip Counters | 0 to 1 | 1 | – | F103 | 0 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 1136 | Clear Event Record | 0 to 1 | 1 | – | F103 | 0 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 1137 | Clear Generator Information | 0 to 1 | 1 | – | F103 | 0 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
1, 2, 3 See Table footnotes on page 39
| 18 | 
http://www.GEindustrial.com/multilin
| GE Multilin | 