GE 1601-0149-A2 manual DNP Point Lists Binary / Frozen Counter Objects 20/21, Counters Point List

Models: 1601-0149-A2

1 62
Download 62 pages 62.7 Kb
Page 56
Image 56

489

Communications Guide

DNP Point Lists

Binary / Frozen Counter (Objects 20/21)

NOTE

Table 7: Counters Point List

INDEX

ROLLOVER

DESCRIPTION

 

POINT

 

 

 

 

 

 

 

0

50000

Number of Breaker Operations

 

 

 

1

50000

Number of Thermal Resets

 

 

 

2

50000

Number of Trips (total)

 

 

 

3

50000

Number of Digital Input Trips

 

 

 

4

50000

Number of Sequential Trips

 

 

 

5

50000

Number of Field-Breaker Discrepancy Trips

 

 

 

6

50000

Number of Tachometer Trips

 

 

 

7

50000

Number of Offline Overcurrent Trips

 

 

 

8

50000

Number of Phase Overcurrent Trips

 

 

 

9

50000

Number of Negative Sequence Overcurrent Trips

 

 

 

10

50000

Number of Ground Overcurrent Trips

 

 

 

11

50000

Number of Phase Differential Trips

 

 

 

12

50000

Number of Undervoltage Trips

 

 

 

13

50000

Number of Overvoltage Trips

 

 

 

14

50000

Number of Volts/Hertz Trips

 

 

 

15

50000

Number of Phase Reversal Trips

 

 

 

16

50000

Number of Underfrequency Trips

 

 

 

17

50000

Number of Overfrequency Trips

 

 

 

18

50000

Number of Neutral Overvoltage (Fundamental) Trips

 

 

 

19

50000

Number of Neutral Undervoltage (Third Harmonic) Trips

 

 

 

20

50000

Number of Reactive Power Trips

 

 

 

21

50000

Number of Reverse Power Trips

 

 

 

22

50000

Number of Underpower Trips

 

 

 

23

50000

Number of Stator RTD Trips

 

 

 

24

50000

Number of Bearing RTD Trips

 

 

 

25

50000

Number of Other RTD Trips

 

 

 

26

50000

Number of Ambient RTD Trips

 

 

 

27

50000

Number of Thermal Model Trips

 

 

 

28

50000

Number of Inadvertent Energization Trips

 

 

 

29

50000

Number of Analog Input 1 Trips

 

 

 

30

50000

Number of Analog Input 2 Trips

 

 

 

31

50000

Number of Analog Input 3 Trips

 

 

 

32

50000

Number of Analog Input 4 Trips

 

 

 

33

50000

Number of Loss of Excitation Circle 1 Trips

 

 

 

34

50000

Number of Loss of Excitation Circle 2 Trips

 

 

 

35

50000

Number of Ground Directional Trips

 

 

 

36

50000

Number of High Set Phase Overcurrent Trips

 

 

 

37

50000

Number of Distance Zone 1 Trips

 

 

 

38

50000

Number of Distance Zone 2 Trips

 

 

 

The counters cannot be cleared with the Freeze/Clear function codes (9/10). Instead, the control relay output block points can be used to clear groups of counters. There is only one copy of each counter, so clearing a counter via Modbus or the front panel display causes the corresponding DNP counter point to be cleared and vice-versa.