Modbus Memory Map

Table 1: 489 Memory Map (Sheet 23 of 29)

489

Communications Guide

ADDR

NAME

RANGE

STEP

UNITS

FORMAT

DEFAULT

 

 

 

 

 

 

 

282A

Time to Trip at 3.75 FLA

5 to 999999

1

s

F10

5

 

 

 

 

 

 

 

282C

Time to Trip at 4.00 FLA

5 to 999999

1

s

F10

5

 

 

 

 

 

 

 

282E

Time to Trip at 4.25 FLA

5 to 999999

1

s

F10

5

 

 

 

 

 

 

 

2830

Time to Trip at 4.50 FLA

5 to 999999

1

s

F10

5

 

 

 

 

 

 

 

2832

Time to Trip at 4.75 FLA

5 to 999999

1

s

F10

5

 

 

 

 

 

 

 

2834

Time to Trip at 5.00 FLA

5 to 999999

1

s

F10

5

 

 

 

 

 

 

 

2836

Time to Trip at 5.50 FLA

5 to 999999

1

s

F10

5

 

 

 

 

 

 

 

2838

Time to Trip at 6.00 FLA

5 to 999999

1

s

F10

5

 

 

 

 

 

 

 

283A

Time to Trip at 6.50 FLA

5 to 999999

1

s

F10

5

 

 

 

 

 

 

 

283C

Time to Trip at 7.00 FLA

5 to 999999

1

s

F10

5

 

 

 

 

 

 

 

283E

Time to Trip at 7.50 FLA

5 to 999999

1

s

F10

5

 

 

 

 

 

 

 

2840

Time to Trip at 8.00 FLA

5 to 999999

1

s

F10

5

 

 

 

 

 

 

 

2842

Time to Trip at 10.0 FLA

5 to 999999

1

s

F10

5

 

 

 

 

 

 

 

2844

Time to Trip at 15.0 FLA

5 to 999999

1

s

F10

5

 

 

 

 

 

 

 

2846

Time to Trip at 20.0 FLA

5 to 999999

1

s

F10

5

 

 

 

 

 

 

 

2848

Minimum Allowable Voltage

70 to 95

1

%

F1

80

 

 

 

 

 

 

 

2849

Stall Current at Minimum Voltage

200 to 1500

1

FLA

F3

480

 

 

 

 

 

 

 

284A

Safe Stall Time at Minimum Voltage

5 to 9999

1

s

F2

200

 

 

 

 

 

 

 

284B

Acceleration Intersect at Minimum Voltage

200 to 1500

1

FLA

F3

380

 

 

 

 

 

 

 

284C

Stall Current at 100% Voltage

200 to 1500

1

FLA

F3

600

 

 

 

 

 

 

 

284D

Safe Stall Time at 100% Voltage

5 to 9999

1

s

F2

100

 

 

 

 

 

 

 

284E

Acceleration Intersect at 100% Voltage

200 to 1500

1

FLA

F3

500

 

 

 

 

 

 

 

THERMAL MODEL / THERMAL ELEMENTS

 

 

 

 

 

 

 

 

 

 

 

 

2900

Thermal Model Alarm

0 to 2

1

F115

0

 

 

 

 

 

 

 

2901

Assign Alarm Relays (2-5)

1 to 4

1

F50

16

 

 

 

 

 

 

 

2902

Thermal Alarm Level

10 to 100

1

%Used

F1

75

 

 

 

 

 

 

 

2903

Thermal Model Alarm Events

0 to 1

1

F105

0

 

 

 

 

 

 

 

2904

Thermal Model Trip

0 to 2

1

F115

0

 

 

 

 

 

 

 

2905

Assign Trip Relays (1-4)

0 to 3

1

F50

1

 

 

 

 

 

 

 

MONITORING / TRIP COUNTER

 

 

 

 

 

 

 

 

 

 

 

 

2A00

Trip Counter Alarm

0 to 2

1

F115

0

 

 

 

 

 

 

 

2A01

Assign Alarm Relays (2-5)

1 to 4

1

F50

16

 

 

 

 

 

 

 

2A02

Trip Counter Alarm Level

1 to 50000

1

Trips

F1

25

 

 

 

 

 

 

 

2A03

Trip Counter Alarm Events

0 to 1

1

F105

0

 

 

 

 

 

 

 

MONITORING / BREAKER FAILURE

 

 

 

 

 

 

 

 

 

 

 

 

2A20

Breaker Failure Alarm

0 to 2

1

F115

0

 

 

 

 

 

 

 

2A21

Assign Alarm Relays (2-5)

1 to 4

1

F50

16

 

 

 

 

 

 

 

2A22

Breaker Failure Level

5 to 2000

1

CT

F3

100

 

 

 

 

 

 

 

2A23

Breaker Failure Delay

10 to 1000

10

ms

F1

100

 

 

 

 

 

 

 

2A24

Breaker Failure Alarm Events

0 to 1

1

F105

0

 

 

 

 

 

 

 

MONITORING / TRIP COIL MONITOR

 

 

 

 

 

 

 

 

 

 

 

 

2A30

Trip Coil Monitor Alarm

0 to 2

1

F115

0

 

 

 

 

 

 

 

2A31

Assign Alarm Relays (2-5)

1 to 4

1

F50

16

 

 

 

 

 

 

 

2A32

Trip Coil Monitor Alarm Events

0 to 1

1

F105

0

 

 

 

 

 

 

 

MONITORING / VT FUSE FAILURE

 

 

 

 

 

 

 

 

 

 

 

 

2A50

VT Fuse Failure Alarm

0 to 2

1

F115

0

 

 

 

 

 

 

 

2A51

Assign Alarm Relays (2-5)

1 to 4

1

F50

16

 

 

 

 

 

 

 

2A52

VT Fuse Failure Alarm Events

0 to 1

1

F105

0

 

 

 

 

 

 

 

MONITORING / CURRENT DEMAND

 

 

 

 

 

 

 

 

 

 

 

 

2A60

Current Demand Period

5 to 90

1

min

F1

15

 

 

 

 

 

 

 

2A61

Current Demand Alarm

0 to 2

1

A

F115

0

 

 

 

 

 

 

 

2A62

Assign Alarm Relays (2-5)

1 to 4

1

A

F50

16

 

 

 

 

 

 

 

2A63

Current Demand Limit

10 to 2000

1

FLA

F14

125

 

 

 

 

 

 

 

1, 2, 3 See Table footnotes on page 39

GE Multilin

http://www.GEindustrial.com/multilin

33

Page 37
Image 37
GE 1601-0149-A2 manual Memory Map Sheet 23