Modbus Memory Map
Table 1: 489 Memory Map (Sheet 23 of 29)
489
Communications Guide
ADDR | NAME | RANGE | STEP | UNITS | FORMAT | DEFAULT |
|
|
|
|
|
|
|
282A | Time to Trip at 3.75 ⋅ FLA | 5 to 999999 | 1 | s | F10 | 5 |
|
|
|
|
|
|
|
282C | Time to Trip at 4.00 ⋅ FLA | 5 to 999999 | 1 | s | F10 | 5 |
|
|
|
|
|
|
|
282E | Time to Trip at 4.25 ⋅ FLA | 5 to 999999 | 1 | s | F10 | 5 |
|
|
|
|
|
|
|
2830 | Time to Trip at 4.50 ⋅ FLA | 5 to 999999 | 1 | s | F10 | 5 |
|
|
|
|
|
|
|
2832 | Time to Trip at 4.75 ⋅ FLA | 5 to 999999 | 1 | s | F10 | 5 |
|
|
|
|
|
|
|
2834 | Time to Trip at 5.00 ⋅ FLA | 5 to 999999 | 1 | s | F10 | 5 |
|
|
|
|
|
|
|
2836 | Time to Trip at 5.50 ⋅ FLA | 5 to 999999 | 1 | s | F10 | 5 |
|
|
|
|
|
|
|
2838 | Time to Trip at 6.00 ⋅ FLA | 5 to 999999 | 1 | s | F10 | 5 |
|
|
|
|
|
|
|
283A | Time to Trip at 6.50 ⋅ FLA | 5 to 999999 | 1 | s | F10 | 5 |
|
|
|
|
|
|
|
283C | Time to Trip at 7.00 ⋅ FLA | 5 to 999999 | 1 | s | F10 | 5 |
|
|
|
|
|
|
|
283E | Time to Trip at 7.50 ⋅ FLA | 5 to 999999 | 1 | s | F10 | 5 |
|
|
|
|
|
|
|
2840 | Time to Trip at 8.00 ⋅ FLA | 5 to 999999 | 1 | s | F10 | 5 |
|
|
|
|
|
|
|
2842 | Time to Trip at 10.0 ⋅ FLA | 5 to 999999 | 1 | s | F10 | 5 |
|
|
|
|
|
|
|
2844 | Time to Trip at 15.0 ⋅ FLA | 5 to 999999 | 1 | s | F10 | 5 |
|
|
|
|
|
|
|
2846 | Time to Trip at 20.0 ⋅ FLA | 5 to 999999 | 1 | s | F10 | 5 |
|
|
|
|
|
|
|
2848 | Minimum Allowable Voltage | 70 to 95 | 1 | % | F1 | 80 |
|
|
|
|
|
|
|
2849 | Stall Current at Minimum Voltage | 200 to 1500 | 1 | ⋅ FLA | F3 | 480 |
|
|
|
|
|
|
|
284A | Safe Stall Time at Minimum Voltage | 5 to 9999 | 1 | s | F2 | 200 |
|
|
|
|
|
|
|
284B | Acceleration Intersect at Minimum Voltage | 200 to 1500 | 1 | ⋅ FLA | F3 | 380 |
|
|
|
|
|
|
|
284C | Stall Current at 100% Voltage | 200 to 1500 | 1 | ⋅ FLA | F3 | 600 |
|
|
|
|
|
|
|
284D | Safe Stall Time at 100% Voltage | 5 to 9999 | 1 | s | F2 | 100 |
|
|
|
|
|
|
|
284E | Acceleration Intersect at 100% Voltage | 200 to 1500 | 1 | ⋅ FLA | F3 | 500 |
|
|
|
|
|
|
|
THERMAL MODEL / THERMAL ELEMENTS |
|
|
|
|
| |
|
|
|
|
|
|
|
2900 | Thermal Model Alarm | 0 to 2 | 1 | – | F115 | 0 |
|
|
|
|
|
|
|
2901 | Assign Alarm Relays | 1 to 4 | 1 | – | F50 | 16 |
|
|
|
|
|
|
|
2902 | Thermal Alarm Level | 10 to 100 | 1 | %Used | F1 | 75 |
|
|
|
|
|
|
|
2903 | Thermal Model Alarm Events | 0 to 1 | 1 | – | F105 | 0 |
|
|
|
|
|
|
|
2904 | Thermal Model Trip | 0 to 2 | 1 | – | F115 | 0 |
|
|
|
|
|
|
|
2905 | Assign Trip Relays | 0 to 3 | 1 | – | F50 | 1 |
|
|
|
|
|
|
|
MONITORING / TRIP COUNTER |
|
|
|
|
| |
|
|
|
|
|
|
|
2A00 | Trip Counter Alarm | 0 to 2 | 1 | – | F115 | 0 |
|
|
|
|
|
|
|
2A01 | Assign Alarm Relays | 1 to 4 | 1 | – | F50 | 16 |
|
|
|
|
|
|
|
2A02 | Trip Counter Alarm Level | 1 to 50000 | 1 | Trips | F1 | 25 |
|
|
|
|
|
|
|
2A03 | Trip Counter Alarm Events | 0 to 1 | 1 | – | F105 | 0 |
|
|
|
|
|
|
|
MONITORING / BREAKER FAILURE |
|
|
|
|
| |
|
|
|
|
|
|
|
2A20 | Breaker Failure Alarm | 0 to 2 | 1 | – | F115 | 0 |
|
|
|
|
|
|
|
2A21 | Assign Alarm Relays | 1 to 4 | 1 | – | F50 | 16 |
|
|
|
|
|
|
|
2A22 | Breaker Failure Level | 5 to 2000 | 1 | ⋅ CT | F3 | 100 |
|
|
|
|
|
|
|
2A23 | Breaker Failure Delay | 10 to 1000 | 10 | ms | F1 | 100 |
|
|
|
|
|
|
|
2A24 | Breaker Failure Alarm Events | 0 to 1 | 1 | – | F105 | 0 |
|
|
|
|
|
|
|
MONITORING / TRIP COIL MONITOR |
|
|
|
|
| |
|
|
|
|
|
|
|
2A30 | Trip Coil Monitor Alarm | 0 to 2 | 1 | – | F115 | 0 |
|
|
|
|
|
|
|
2A31 | Assign Alarm Relays | 1 to 4 | 1 | – | F50 | 16 |
|
|
|
|
|
|
|
2A32 | Trip Coil Monitor Alarm Events | 0 to 1 | 1 | – | F105 | 0 |
|
|
|
|
|
|
|
MONITORING / VT FUSE FAILURE |
|
|
|
|
| |
|
|
|
|
|
|
|
2A50 | VT Fuse Failure Alarm | 0 to 2 | 1 | – | F115 | 0 |
|
|
|
|
|
|
|
2A51 | Assign Alarm Relays | 1 to 4 | 1 | – | F50 | 16 |
|
|
|
|
|
|
|
2A52 | VT Fuse Failure Alarm Events | 0 to 1 | 1 | – | F105 | 0 |
|
|
|
|
|
|
|
MONITORING / CURRENT DEMAND |
|
|
|
|
| |
|
|
|
|
|
|
|
2A60 | Current Demand Period | 5 to 90 | 1 | min | F1 | 15 |
|
|
|
|
|
|
|
2A61 | Current Demand Alarm | 0 to 2 | 1 | A | F115 | 0 |
|
|
|
|
|
|
|
2A62 | Assign Alarm Relays | 1 to 4 | 1 | A | F50 | 16 |
|
|
|
|
|
|
|
2A63 | Current Demand Limit | 10 to 2000 | 1 | ⋅ FLA | F14 | 125 |
|
|
|
|
|
|
|
1, 2, 3 See Table footnotes on page 39