489

 

 

 

 

Modbus Memory Map

 

Communications Guide

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 1: 489 Memory Map (Sheet 28 of 29)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ADDR

NAME

RANGE

STEP

UNITS

FORMAT

DEFAULT

 

 

 

 

 

 

 

 

 

 

2D2A

Pre-Fault System Frequency

50 to 900

1

Hz

F2

600

 

 

 

 

 

 

 

 

 

 

 

2D2B

Pre-Fault Analog Input 1

0 to 100

1

%

F1

0

 

 

 

 

 

 

 

 

 

 

 

2D2C

Pre-Fault Analog Input 2

0 to 100

1

%

F1

0

 

 

 

 

 

 

 

 

 

 

 

2D2D

Pre-Fault Analog Input 3

0 to 100

1

%

F1

0

 

 

 

 

 

 

 

 

 

 

 

2D2E

Pre-Fault Analog Input 4

0 to 100

1

%

F1

0

 

 

 

 

 

 

 

 

 

 

 

2D4C

Pre-Fault Stator RTD Temp

–50 to 250

1

°F

F4

40

 

 

 

 

 

 

 

 

 

 

 

2D4D

Pre-Fault Bearing RTD Temp

–50 to 250

1

°F

F4

40

 

 

 

 

 

 

 

 

 

 

 

2D4E

Pre-Fault Other RTD Temp

–50 to 250

1

°F

F4

40

 

 

 

 

 

 

 

 

 

 

 

2D4F

Pre-Fault Ambient RTD Temp

–50 to 250

1

°F

F4

40

 

 

 

 

 

 

 

 

 

 

 

489 TESTING / FAULT SETUP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2D80

Fault Iphase Output

0 to 2000

1

CT

F3

0

 

 

 

 

 

 

 

 

 

 

 

2D81

Fault Voltages Phase-N

0 to 150

1

Rated

F3

100

 

 

 

 

 

 

 

 

 

 

 

2D82

Fault Current Lags Voltage

0 to 359

1

°

F1

0

 

 

 

 

 

 

 

 

 

 

 

2D83

Fault Iphase Neutral

0 to 2000

1

CT

F3

0

 

 

 

 

 

 

 

 

 

 

 

2D84

Fault Current Ground

0 to 2000

1

CT

F3

0

 

 

 

 

 

 

 

 

 

 

 

2D85

Fault Voltage Neutral

0 to 1000

1

Volts

F2

0

 

 

 

 

 

 

 

 

 

 

 

2D86

Fault Stator RTD Temp

–50 to 250

1

°C

F4

40

 

 

 

 

 

 

 

 

 

 

 

2D87

Fault Bearing RTD Temp

–50 to 250

1

°C

F4

40

 

 

 

 

 

 

 

 

 

 

 

2D88

Fault Other RTD Temp

–50 to 250

1

°C

F4

40

 

 

 

 

 

 

 

 

 

 

 

2D89

Fault Ambient RTD Temp

–50 to 250

1

°C

F4

40

 

 

 

 

 

 

 

 

 

 

 

2D8A

Fault System Frequency

50 to 900

1

Hz

F2

600

 

 

 

 

 

 

 

 

 

 

 

2D8B

Fault Analog Input 1

0 to 100

1

%

F1

0

 

 

 

 

 

 

 

 

 

 

 

2D8C

Fault Analog Input 2

0 to 100

1

%

F1

0

 

 

 

 

 

 

 

 

 

 

 

2D8D

Fault Analog Input 3

0 to 100

1

%

F1

0

 

 

 

 

 

 

 

 

 

 

 

2D8E

Fault Analog Input 4

0 to 100

1

%

F1

0

 

 

 

 

 

 

 

 

 

 

 

2DBC

Fault Stator RTD Temp

–50 to 250

1

°F

F4

40

 

 

 

 

 

 

 

 

 

 

 

2DBD

Fault Bearing RTD Temp

–50 to 250

1

°F

F4

40

 

 

 

 

 

 

 

 

 

 

 

2DBE

Fault Other RTD Temp

–50 to 250

1

°F

F4

40

 

 

 

 

 

 

 

 

 

 

 

2DBF

Fault Ambient RTD Temp

–50 to 250

1

°F

F4

40

 

 

 

 

 

 

 

 

 

 

 

489 TESTING / TEST OUTPUT RELAYS

 

 

 

 

 

 

2DE0 Force Operation Of Relays

0 to 8

1

F139

0

489 TESTING / TEST ANALOG OUTPUT

2DF0

Force Analog Outputs Function

0 to 1

1

F126

0

 

 

 

 

 

 

 

2DF1

Analog Output 1 Forced Value

0 to 100

1

%

F1

0

 

 

 

 

 

 

 

2DF2

Analog Output 2 Forced Value

0 to 100

1

%

F1

0

 

 

 

 

 

 

 

2DF3

Analog Output 3 Forced Value

0 to 100

1

%

F1

0

 

 

 

 

 

 

 

2DF4

Analog Output 4 Forced Value

0 to 100

1

%

F1

0

 

 

 

 

 

 

 

EVENT RECORDER / GENERAL

 

 

 

 

 

 

 

 

 

 

 

 

3000

Event Recorder Last Reset Date (2 Words)

N/A

N/A

N/A

F18

N/A

 

 

 

 

 

 

 

3002

Total Number Of Events Since Last Clear

0 to 65535

1

N/A

F1

N/A

 

 

 

 

 

 

 

3003

Event Record Selector

0 to 65535

1

F1

0

 

 

 

 

 

 

 

EVENT RECORDER / SELECTED EVENT

 

 

 

 

 

 

 

 

 

 

 

 

3004

Cause Of Event

0 to 139

1

F134

0

 

 

 

 

 

 

 

3005

Time Of Event (2 Words)

N/A

N/A

N/A

F19

N/A

 

 

 

 

 

 

 

3007

Date Of Event (2 Words)

N/A

N/A

N/A

F18

N/A

 

 

 

 

 

 

 

3009

Tachometer

0 to 7200

1

RPM

F1

0

 

 

 

 

 

 

 

300A

Phase A Current

0 to 999999

1

Amps

F12

0

 

 

 

 

 

 

 

300C

Phase B Current

0 to 999999

1

Amps

F12

0

 

 

 

 

 

 

 

300E

Phase C Current

0 to 999999

1

Amps

F12

0

 

 

 

 

 

 

 

3010

Phase A Differential Current

0 to 999999

1

Amps

F12

0

 

 

 

 

 

 

 

3012

Phase B Differential Current

0 to 999999

1

Amps

F12

0

 

 

 

 

 

 

 

3014

Phase C Differential Current

0 to 999999

1

Amps

F12

0

 

 

 

 

 

 

 

3016

Neg. Seq. Current

0 to 2000

1

%FLA

F1

0

 

 

 

 

 

 

 

1, 2, 3 See Table footnotes on page 39

38

http://www.GEindustrial.com/multilin

GE Multilin

Page 42
Image 42