Modbus Functions

Function Code 16: Store Multiple Setpoints

489

Communications Guide

Modbus Implementation: Preset Multiple Registers

489 Implementation: Store Multiple Setpoints

This function code allows multiple Setpoints to be stored into the 489 memory. Modbus “registers” are 16-bit (two byte) values transmitted high order byte first. Thus all 489 setpoints are sent as two bytes. The maximum number of Setpoints that can be stored in one transmission is dependent on the slave device. Modbus allows up to a maximum of 60 holding registers to be stored. The 489 response to this function code is to echo the slave address, function code, starting address, the number of Setpoints stored, and the CRC.

Message Format and Example:

Request slave 11 to store the value 01F4 to Setpoint address 1180 and the value 0001 to setpoint address 1181. After the transmission in this example is complete,

489 slave 11 will have the following setpoints information stored:

Address

 

Data

 

 

 

 

 

 

 

 

 

 

 

1180

 

01F4

 

 

 

 

 

 

 

 

 

 

 

1181

 

0001

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Master Transmission

Bytes

Example

Description

 

 

 

 

 

 

 

 

 

 

Slave Address

 

1

0B

message for slave 11

 

 

 

 

 

Function Code

 

1

10

store setpoints

 

 

 

 

Data Starting Address

2

11 80

data starting at 1180h

 

 

 

 

Number of Setpoints

2

00 02

2 setpoints = 4 bytes total

 

 

 

 

 

Byte Count

 

1

04

2 registers = 4 bytes

 

 

 

 

 

Data 1

 

2

01 F4

data for address 1180h

 

 

 

 

 

Data 2

 

2

00 01

data for address 1181h

 

 

 

 

 

CRC (low, high)

 

2

9B 89

computed CRC error code

 

 

 

 

 

 

 

 

 

 

Slave Response

 

Bytes

Example

Description

 

 

 

 

 

 

 

 

 

 

Slave Address

 

1

0B

message from slave 11

 

 

 

 

 

Function Code

 

1

10

store multiple setpoints

 

 

 

 

Data Starting Address

2

11 80

data starting at 1180h

 

 

 

 

Number of Setpoints

2

00 02

2 setpoints (4 bytes total)

 

 

 

 

 

CRC (low, high)

 

2

45 B6

computed CRC error code

 

 

 

 

 

 

 