Modbus Memory Map

Table 2: Data Formats (Sheet 11 of 12)

CODE

TYPE

DEFINITION

 

 

 

F208

Unsigned

UNDERVOLTAGE TRIP

 

16 bit

ELEMENT TYPE

 

integer

 

 

 

 

 

0

Curve

 

 

 

 

1

Definite Time

 

 

 

F209

Unsigned

BREAKER OPERATION

 

16 bit

TYPE

 

integer

 

 

 

 

 

0

Breaker Auxiliary A

 

 

 

 

1

Breaker Auxiliary B

 

 

 

F210

Unsigned

ASSIGNABLE INPUT

 

16 bit

SELECTION

 

integer

 

 

 

 

 

0

None

 

 

 

 

1

Input 1

 

 

 

 

2

Input 2

 

 

 

 

3

Input 3

 

 

 

 

4

Input 4

 

 

 

 

5

Input 5

 

 

 

 

6

Input 6

 

 

 

 

7

Input 7

 

 

 

F211

Unsigned

VOLTS/HERTZ

 

16 bit

ELEMENT TYPE

 

integer

 

 

 

 

 

0

Curve #1

 

 

 

 

1

Curve #2

 

 

 

 

2

Curve #3

 

 

 

 

3

Definite Time

 

 

 

F212

Unsigned

RTD NUMBER

 

16 bit

 

 

integer

 

 

 

 

 

0

All

 

 

 

 

1

RTD #1

 

 

 

 

2

RTD #2

 

 

 

 

3

RTD #3

 

 

 

 

4

RTD #4

 

 

 

 

5

RTD #5

 

 

 

 

6

RTD #6

 

 

 

 

7

RTD #7

 

 

 

 

8

RTD #8

 

 

 

 

9

RTD #9

 

 

 

 

10

RTD #10

 

 

 

 

11

RTD #11

 

 

 

 

12

RTD #12

 

 

 

F213

Unsigned

COMMUNICATIONS

 

16 bit

MONITOR PORT

 

integer

SELECTION

 

 

 

 

0

Computer RS485

 

 

 

 

1

Auxiliary RS485

 

 

 

 

2

Front Panel RS232

 

 

 

489

Communications Guide

Table 2: Data Formats (Sheet 12 of 12)

CODE

TYPE

DEFINITION

 

 

 

F214

Unsigned

WAVEFORM MEMORY

 

16 bit

CHANNEL SELECTOR

 

integer

 

 

 

 

 

0

Phase A Line Current

 

 

512 counts = 1 CT

 

 

 

 

1

Phase B Line Current

 

 

512 counts = 1 CT

 

 

 

 

2

Phase C Line Current

 

 

512 counts = 1 CT

 

 

 

 

3

Phase A Line Current

 

 

512 counts = 1 CT

 

 

 

 

4

Neutral-End Phase A Line

 

 

Current

 

 

512 counts = 1 CT

 

 

 

 

5

Neutral-End Phase B Line

 

 

Current

 

 

512 counts = 1 CT

 

 

 

 

6

Neutral-End Phase C Line

 

 

Current

 

 

512 counts = 1 CT

 

 

 

 

7

Phase A to Neutral

 

 

Voltage; 3500 counts =

 

 

120 secondary volts

 

 

 

 

8

Phase B to Neutral

 

 

Voltage; 3500 counts =

 

 

120 secondary volts

 

 

 

 

9

Phase C to Neutral

 

 

Voltage; 3500 counts =

 

 

120 secondary volts

 

 

 

F215

Unsigned

CURRENT SOURCE

 

16 bit

 

 

integer

 

 

 

 

 

0

Neutral-End CTs

 

 

 

 

1

Output-End CTs

 

 

 

F216

Unsigned

DNP PORT SELECTION

 

16 bit

 

 

integer

 

 

 

 

 

0

None

 

 

 

 

1

Computer RS485

 

 

 

 

2

Auxiliary RS485

 

 

 

 

3

Front Panel RS485

 

 

 

F217

Unsigned

GROUND

 

16 bit

DIRECTIONAL MTA

 

integer

 

 

 

 

 

0

0 degrees

 

 

 

 

1

90 degrees

 

 

 

 

2

180 degrees

 

 

 

 

3

270 degrees

 

 

 

F218

Unsigned

BREAKER STATE

 

16 bit

 

 

integer

 

 

 

 

 

0

52 Closed

 

 

 

 

1

52 Open/Closed

 

 

 

F219

Unsigned

STEP-UP

 

16 bit

TRANSFORMER TYPE

 

integer

 

 

 

 

 

0

None

 

 

 

 

1

Delta/Wye

 

 

 

F220

Unsigned

IRIG-B TYPE

 

16 bit

 

 

integer

 

 

 

 

 

0

None

 

 

 

 

1

DC Shift

 

 

 

 

2

Amplitude Modulated

 

 

 

GE Multilin

http://www.GEindustrial.com/multilin

45

Page 49
Image 49
GE 1601-0149-A2 Undervoltage Trip, Element Type, Breaker Operation, Assignable Input, Volts/Hertz, RTD Number, Ground