Modbus Memory Map

Table 1: 489 Memory Map (Sheet 21 of 29)

489

Communications Guide

ADDR

NAME

RANGE

STEP

UNITS

FORMAT

DEFAULT

 

 

 

 

 

 

 

2566

RTD #6 Trip Voting

1 to 12

1

F122

6

 

 

 

 

 

 

 

2567

Assign Trip Relays (1-4)

0 to 3

1

F50

1

 

 

 

 

 

 

 

2568

RTD #6 Trip Temperature

1 to 250

1

°C

F1

155

 

 

 

 

 

 

 

2569

RTD #6 Name

0 to 8

1

F22

_

 

 

 

 

 

 

 

RTD TEMPERATURE / RTD #7

 

 

 

 

 

 

 

 

 

 

 

 

25A0

RTD #7 Application

0 to 4

1

F121

2

 

 

 

 

 

 

 

25A1

RTD #7 Alarm

0 to 2

1

F115

0

 

 

 

 

 

 

 

25A2

Assign Alarm Relays (2-5)

1 to 4

1

F50

16

 

 

 

 

 

 

 

25A3

RTD #7 Alarm Temperature

1 to 250

1

°C

F1

80

 

 

 

 

 

 

 

25A4

RTD #7 Alarm Events

0 to 1

1

F105

0

 

 

 

 

 

 

 

25A5

RTD #7 Trip

0 to 2

1

F115

0

 

 

 

 

 

 

 

25A6

RTD #7 Trip Voting

1 to 12

1

F122

7

 

 

 

 

 

 

 

25A7

Assign Trip Relays (1-4)

0 to 3

1

F50

1

 

 

 

 

 

 

 

25A8

RTD #7 Trip Temperature

1 to 250

1

°C

F1

90

 

 

 

 

 

 

 

25A9

RTD #7 Name

0 to 8

1

F22

_

 

 

 

 

 

 

 

RTD TEMPERATURE / RTD #8

 

 

 

 

 

 

 

 

 

 

 

 

25E0

RTD #8 Application

0 to 4

1

F121

2

 

 

 

 

 

 

 

25E1

RTD #8 Alarm

0 to 2

1

F115

0

 

 

 

 

 

 

 

25E2

Assign Alarm Relays (2-5)

1 to 4

1

F50

16

 

 

 

 

 

 

 

25E3

RTD #8 Alarm Temperature

1 to 250

1

°C

F1

80

 

 

 

 

 

 

 

25E4

RTD #8 Alarm Events

0 to 1

1

F105

0

 

 

 

 

 

 

 

25E5

RTD #8 Trip

0 to 2

1

F115

0

 

 

 

 

 

 

 

25E6

RTD #8 Trip Voting

1 to 12

1

F122

8

 

 

 

 

 

 

 

25E7

Assign Trip Relays (1-4)

0 to 3

1

F50

1

 

 

 

 

 

 

 

25E8

RTD #8 Trip Temperature

1 to 250

1

°C

F1

90

 

 

 

 

 

 

 

25E9

RTD #8 Name

0 to 8

1

F22

_

 

 

 

 

 

 

 

RTD TEMPERATURE / RTD #9

 

 

 

 

 

 

 

 

 

 

 

 

2620

RTD #9 Application

0 to 4

1

F121

2

 

 

 

 

 

 

 

2621

RTD #9 Alarm

0 to 2

1

F115

0

 

 

 

 

 

 

 

2622

Assign Alarm Relays (2-5)

1 to 4

1

F50

16

 

 

 

 

 

 

 

2623

RTD #9 Alarm Temperature

1 to 250

1

°C

F1

80

 

 

 

 

 

 

 

2624

RTD #9 Alarm Events

0 to 1

1

F105

0

 

 

 

 

 

 

 

2625

RTD #9 Trip

0 to 2

1

F115

0

 

 

 

 

 

 

 

2626

RTD #9 Trip Voting

1 to 12

1

F122

9

 

 

 

 

 

 

 

2627

Assign Trip Relays (1-4)

0 to 3

1

F50

1

 

 

 

 

 

 

 

2628

RTD #9 Trip Temperature

1 to 250

1

°C

F1

90

 

 

 

 

 

 

 

2629

RTD #9 Name

0 to 8

1

F22

_

 

 

 

 

 

 

 

RTD TEMPERATURE / RTD #10

 

 

 

 

 

 

 

 

 

 

 

 

2660

RTD #10 Application

0 to 4

1

F121

2

 

 

 

 

 

 

 

2661

RTD #10 Alarm

0 to 2

1

F115

0

 

 

 

 

 

 

 

2662

Assign Alarm Relays (2-5)

1 to 4

1

F50

16

 

 

 

 

 

 

 

2663

RTD #10 Alarm Temperature

1 to 250

1

°C

F1

80

 

 

 

 

 

 

 

2664

RTD #10 Alarm Events

0 to 1

1

F105

0

 

 

 

 

 

 

 

2665

RTD #10 Trip

0 to 2

1

F115

0

 

 

 

 

 

 

 

2666

RTD #10 Trip Voting

1 to 12

1

F122

10

 

 

 

 

 

 

 

2667

Assign Trip Relays (1-4)

0 to 3

1

F50

1

 

 

 

 

 

 

 

2668

RTD #10 Trip Temperature

1 to 250

1

°C

F1

90

 

 

 

 

 

 

 

2669

RTD #10 Name

0 to 8

1

F22

_

 

 

 

 

 

 

 

RTD TEMPERATURE / RTD #11

 

 

 

 

 

 

 

 

 

 

 

 

26A0

RTD #11 Application

0 to 4

1

F121

4

 

 

 

 

 

 

 

26A1

RTD #11 Alarm

0 to 2

1

F115

0

 

 

 

 

 

 

 

26A2

Assign Alarm Relays (2-5)

1 to 4

1

F50

16

 

 

 

 

 

 

 

26A3

RTD #11 Alarm Temperature

1 to 250

1

°C

F1

80

 

 

 

 

 

 

 