Table 1: 489 Memory Map (Sheet 17 of 29)

489

Communications Guide

ADDR

NAME

RANGE

STEP

UNITS

FORMAT

DEFAULT

 

 

 

 

 

 

 

2009

Undervoltage Curve Reset Rate

0 to 9999

1

s

F2

14

 

 

 

 

 

 

 

200A

Undervoltage Curve Element

0 to 1

1

F208

0

 

 

 

 

 

 

 

VOLTAGE ELEMENTS / OVERVOLTAGE

 

 

 

 

 

 

 

 

 

 

 

 

2020

Overvoltage Alarm

0 to 2

1

F115

0

 

 

 

 

 

 

 

2021

Assign Alarm Relays (2-5)

1 to 4

1

F50

16

 

 

 

 

 

 

 

2022

Overvoltage Alarm Pickup

101 to 150

1

Rated

F3

115

 

 

 

 

 

 

 

2023

Overvoltage Alarm Delay

1 to 1200

1

s

F2

30

 

 

 

 

 

 

 

2024

Overvoltage Alarm Events

0 to 1

1

F105

0

 

 

 

 

 

 

 

2025

Overvoltage Trip

0 to 2

1

F115

0

 

 

 

 

 

 

 

2026

Assign Trip Relays (1-4)

0 to 3

1

F50

1

 

 

 

 

 

 

 

2027

Overvoltage Trip Pickup

101 to 150

1

Rated

F3

120

 

 

 

 

 

 

 

2028

Overvoltage Trip Delay

1 to 100

1

s

F2

10

 

 

 

 

 

 

 

2029

Overvoltage Curve Reset Rate

0 to 9999

1

s

F2

14

 

 

 

 

 

 

 

202A

Overvoltage Curve Element

0 to 1

1

F208

0

 

 

 

 

 

 

 

VOLTAGE ELEMENTS / VOLTS/HERTZ

 

 

 

 

 

 

 

 

 

 

 

 

2040

Volts/Hertz Alarm

0 to 2

1

F115

0

 

 

 

 

 

 

 

2041

Assign Alarm Relays (2-5)

1 to 4

1

F50

16

 

 

 

 

 

 

 

2042

Volts/Hertz Alarm Pickup

50 to 199

1

Nominal

F3

100

 

 

 

 

 

 

 

2043

Volts/Hertz Alarm Delay

1 to 1500

1

s

F2

30

 

 

 

 

 

 

 

2044

Volts/Hertz Alarm Events

0 to 1

1

F105

0

 

 

 

 

 

 

 

2045

Volts/Hertz Trip

0 to 2

1

F115

0

 

 

 

 

 

 

 

2046

Assign Trip Relays (1-4)

0 to 3

1

F50

1

 

 

 

 

 

 

 

2047

Volts/Hertz Trip Pickup

50 to 199

1

Nominal

F3

100

 

 

 

 

 

 

 

2048

Volts/Hertz Trip Delay

1 to 1500

1

s

F2

10

 

 

 

 

 

 

 

2049

Volts/Hertz Curve Reset Rate

0 to 9999

1

s

F2

14

 

 

 

 

 

 

 

204A

Volts/Hertz Trip Element

0 to 3

1

F211

0

 

 

 

 

 

 

 

VOLTAGE ELEMENTS / PHASE REVERSAL

 

 

 

 

 

 

 

 

 

 

 

 

2060

Phase Reversal Trip

0 to 2

1

F115

0

 

 

 

 

 

 

 

2061

Assign Trip Relays (1-4)

0 to 3

1

F50

1

 

 

 

 

 

 

 

VOLTAGE ELEMENTS / UNDERFREQUENCY

 

 

 

 

 

 

 

 

 

 

 

 

2080

Block Underfrequency From Online

0 to 5

1

s

F1

1

 

 

 

 

 

 

 

2081

Voltage Level Cutoff

50 to 99

1

Rated

F3

50

 

 

 

 

 

 

 

2082

Underfrequency Alarm

0 to 2

1

F115

0

 

 

 

 

 

 

 

2083

Assign Alarm Relays (2-5)

1 to 4

1

F50

16

 

 

 

 

 

 

 

2084

Underfrequency Alarm Level

2000 to 6000

1

Hz

F3

5950

 

 

 

 

 

 

 

2085

Underfrequency Alarm Delay

1 to 50000

1

s

F2

50

 

 

 

 

 

 

 

2086

Underfrequency Alarm Events

0 to 1

1

F105

0

 

 

 

 

 

 

 

2087

Underfrequency Trip

0 to 2

1

F115

0

 

 

 

 

 

 

 

2088

Assign Trip Relays (1-4)

0 to 3

1

F50

1

 

 

 

 

 

 

 

2089

Underfrequency Trip Level 1

2000 to 6000

1

Hz

F3

5950

 

 

 

 

 

 

 

208A

Underfrequency Trip Delay 1

1 to 50000

1

s

F2

600

 

 

 

 

 

 

 

208B

Underfrequency Trip Level 2

2000 to 6000

1

Hz

F3

5800

 

 

 

 

 

 

 

208C

Underfrequency Trip Delay 2

1 to 50000

1

s

F2

300

 

 

 

 

 

 

 

VOLTAGE ELEMENTS / OVERFREQUENCY

 

 

 

 

 

 

 

 

 

 

 

 

20A0

Block Overfrequency From Online

0 to 5

1

s

F1

1

 

 

 

 

 

 

 

20A1

Voltage Level Cutoff

50 to 99

1

Rated

F3

50

 

 

 

 

 

 

 

20A2

Overfrequency Alarm

0 to 2

1

F115

0

 

 

 

 

 

 

 

20A3

Assign Alarm Relays (2-5)

1 to 4

1

F50

16

 

 

 

 

 

 

 

20A4

Overfrequency Alarm Level

2501 to 7000

1

Hz

F3

6050

 

 

 

 

 

 

 

20A5

Overfrequency Alarm Delay

1 to 50000

1

s

F2

50

 

 

 

 

 

 

 

20A6

Overfrequency Alarm Events

0 to 1

1

F105

0

 

 

 

 

 

 

 

20A7

Overfrequency Trip

0 to 2

1

F115

0

 

 

 

 

 

 

 

20A8

Assign Trip Relays (1-4)

0 to 3

1

F50

1

 

 

 

 

 

 

 