Modbus Memory Map
Table 1: 489 Memory Map (Sheet 11 of 29)
489
Communications Guide
ADDR | NAME | RANGE | STEP | UNITS | FORMAT | DEFAULT |
|
|
|
|
|
|
|
12B2 | Input Name | 0 to 12 | 1 | – | F22 | _ |
|
|
|
|
|
|
|
12B8 | Block Input From Online | 0 to 5000 | 1 | s | F1 | 0 |
|
|
|
|
|
|
|
12B9 | General Input F Control | 0 to 1 | 1 | – | F105 | 0 |
|
|
|
|
|
|
|
12BA | Pulsed Control Relay Dwell Time | 0 to 250 | 1 | s | F2 | 0 |
|
|
|
|
|
|
|
12BB | Assign Control Relays | 0 to 4 | 1 | – | F50 | 0 |
|
|
|
|
|
|
|
12BC | General Input F Control Events | 0 to 1 | 1 | – | F105 | 0 |
|
|
|
|
|
|
|
12BD | General Input F Alarm | 0 to 2 | 1 | – | F115 | 0 |
|
|
|
|
|
|
|
12BE | Assign Alarm Relays | 1 to 4 | 1 | – | F50 | 16 |
|
|
|
|
|
|
|
12BF | General Input F Alarm Delay | 1 to 50000 | 1 | s | F2 | 50 |
|
|
|
|
|
|
|
12C0 | General Input F Alarm Events | 0 to 1 | 1 | – | F105 | 0 |
|
|
|
|
|
|
|
12C1 | General Input F Trip | 0 to 2 | 1 | – | F115 | 0 |
|
|
|
|
|
|
|
12C2 | Assign Trip Relays | 0 to 3 | 1 | – | F50 | 1 |
|
|
|
|
|
|
|
12C3 | General Input F Trip Delay | 1 to 50000 | 1 | s | F2 | 50 |
|
|
|
|
|
|
|
DIGITAL INPUTS / GENERAL INPUT G |
|
|
|
|
| |
|
|
|
|
|
|
|
12D0 | Assign Digital Input | 0 to 7 | 1 | – | F210 | 0 |
|
|
|
|
|
|
|
12D1 | Asserted Digital Input State | 0 to 1 | 1 | – | F131 | 0 |
|
|
|
|
|
|
|
12D2 | Input Name | 0 to 12 | 1 | – | F22 | _ |
|
|
|
|
|
|
|
12D8 | Block Input From Online | 0 to 5000 | 1 | s | F1 | 0 |
|
|
|
|
|
|
|
12D9 | General Input G Control | 0 to 1 | 1 | – | F105 | 0 |
|
|
|
|
|
|
|
12DA | Pulsed Control Relay Dwell Time | 0 to 250 | 1 | s | F2 | 0 |
|
|
|
|
|
|
|
12DB | Assign Control Relays | 0 to 4 | 1 | – | F50 | 0 |
|
|
|
|
|
|
|
12DC | General Input G Control Events | 0 to 1 | 1 | – | F105 | 0 |
|
|
|
|
|
|
|
12DD | General Input G Alarm | 0 to 2 | 1 | – | F115 | 0 |
|
|
|
|
|
|
|
12DE | Assign Alarm Relays | 1 to 4 | 1 | – | F50 | 16 |
|
|
|
|
|
|
|
12DF | General Input G Alarm Delay | 1 to 50000 | 1 | s | F2 | 50 |
|
|
|
|
|
|
|
12E0 | General Input G Alarm Events | 0 to 1 | 1 | – | F105 | 0 |
|
|
|
|
|
|
|
12E1 | General Input G Trip | 0 to 2 | 1 | – | F115 | 0 |
|
|
|
|
|
|
|
12E2 | Assign Trip Relays | 0 to 3 | 1 | – | F50 | 1 |
|
|
|
|
|
|
|
12E3 | General Input G Trip Delay | 1 to 50000 | 1 | s | F2 | 50 |
|
|
|
|
|
|
|
DIGITAL INPUTS / REMOTE RESET |
|
|
|
|
| |
|
|
|
|
|
|
|
1300 | Assign Digital Input | 0 to 7 | 1 | – | F210 | 0 |
|
|
|
|
|
|
|
DIGITAL INPUTS / TEST INPUT |
|
|
|
|
| |
|
|
|
|
|
|
|
1310 | Assign Digital Input | 0 to 7 | 1 | – | F210 | 0 |
|
|
|
|
|
|
|
DIGITAL INPUTS / THERMAL RESET |
|
|
|
|
|
1320 Assign Digital Input
0 to 7
1
–
F210
0
DIGITAL INPUTS / DUAL SETPOINTS
1340 | Assign Digital Input | 0 to 7 | 1 | – | F210 | 0 |
|
|
|
|
|
|
|
1341 | Active Setpoint Group | 0 to 1 | 1 | – | F118 | 0 |
|
|
|
|
|
|
|
1342 | Edit Setpoint Group | 0 to 1 | 1 | – | F118 | 0 |
|
|
|
|
|
|
|
DIGITAL INPUTS / SEQUENTIAL TRIP |
|
|
|
|
| |
|
|
|
|
|
|
|
1360 | Assign Digital Input | 0 to 7 | 1 | – | F210 | 0 |
|
|
|
|
|
|
|
1361 | Sequential Trip Type | 0 to 1 | 1 | – | F206 | 0 |
|
|
|
|
|
|
|
1362 | Assign Trip Relays | 0 to 3 | 1 | – | F50 | 1 |
|
|
|
|
|
|
|
1363 | Sequential Trip Level | 2 to 99 | 1 | ⋅ Rated MW | F14 | 5 |
|
|
|
|
|
|
|
1365 | Sequential Trip Delay | 2 to 1200 | 1 | s | F2 | 10 |
|
|
|
|
|
|
|
DIGITAL INPUTS / |
|
|
|
|
| |
|
|
|
|
|
|
|
1380 | Assign Digital Input | 0 to 7 | 1 | – | F210 | 0 |
|
|
|
|
|
|
|
1381 | Field Status Contact | 0 to 1 | 1 | – | F109 | 0 |
|
|
|
|
|
|
|
1382 | Assign Trip Relays | 0 to 3 | 1 | – | F50 | 1 |
|
|
|
|
|
|
|
1383 | 1 to 5000 | 1 | s | F2 | 10 | |
|
|
|
|
|
|
|
DIGITAL INPUTS / TACHOMETER |
|
|
|
|
| |
|
|
|
|
|
|
|
13A0 | Assign Digital Input | 0 to 7 | 1 | – | F210 | 0 |
|
|
|
|
|
|
|
13A1 | Rated Speed | 100 to 3600 | 1 | RPM | F1 | 3600 |
|
|
|
|
|
|
|
1, 2, 3 See Table footnotes on page 39
GE Multilin |
http://www.GEindustrial.com/multilin
21 |