489

 

 

 

 

Modbus Memory Map

 

Communications Guide

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 1: 489 Memory Map (Sheet 24 of 29)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ADDR

NAME

RANGE

STEP

UNITS

FORMAT

DEFAULT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2A65

Current Demand Alarm Events

0 to 1

1

A

F105

0

 

 

 

 

 

 

 

 

 

 

 

MONITORING / MW DEMAND

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2A70

MW Demand Period

5 to 90

1

min

F1

15

 

 

 

 

 

 

 

 

 

 

 

2A71

MW Demand Alarm

0 to 2

1

F115

0

 

 

 

 

 

 

 

 

 

 

 

2A72

Assign Alarm Relays (2-5)

1 to 4

1

F50

16

 

 

 

 

 

 

 

 

 

 

 

2A73

MW Demand Limit

10 to 200

1

Rated

F14

125

 

 

 

 

 

 

 

 

 

 

 

2A75

MW Demand Alarm Events

0 to 1

1

F105

0

 

 

 

 

 

 

 

 

 

 

 

MONITORING / Mvar DEMAND

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2A80

Mvar Demand Period

5 to 90

1

min

F1

15

 

 

 

 

 

 

 

 

 

 

 

2A81

Mvar Demand Alarm

0 to 2

1

F115

0

 

 

 

 

 

 

 

 

 

 

 

2A82

Assign Alarm Relays (2-5)

1 to 4

1

F50

16

 

 

 

 

 

 

 

 

 

 

 

2A83

Mvar Demand Limit

10 to 200

1

Rated

F14

125

 

 

 

 

 

 

 

 

 

 

 

2A85

Mvar Demand Alarm Events

0 to 1

1

F105

0

 

 

 

 

 

 

 

 

 

 

 

MONITORING / MVA DEMAND

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2A90

MVA Demand Period

5 to 90

1

min

F1

15

 

 

 

 

 

 

 

 

 

 

 

2A91

MVA Demand Alarm

0 to 2

1

F115

0

 

 

 

 

 

 

 

 

 

 

 

2A92

Assign Alarm Relays (2-5)

1 to 4

1

F50

16

 

 

 

 

 

 

 

 

 

 

 

2A93

MVA Demand Limit

10 to 200

1

Rated

F14

125

 

 

 

 

 

 

 

 

 

 

 

2A95

MVA Demand Alarm Events

0 to 1

1

F105

0

 

 

 

 

 

 

 

 

 

 

 

MONITORING / PULSE OUTPUT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2AB0

Positive kWh Pulse Output Relays (2-5)

1 to 4

1

F50

0

 

 

 

 

 

 

 

 

 

 

 

2AB1

Positive kWh Pulse Output Interval

1 to 50000

1

F1

10

 

 

 

 

 

 

 

 

 

 

 

2AB2

Positive kvarh Pulse Output Relays (2-5)

1 to 4

1

F50

0

 

 

 

 

 

 

 

 

 

 

 

2AB3

Positive kvarh Pulse Output Interval

1 to 50000

1

F1

10

 

 

 

 

 

 

 

 

 

 

 

2AB4

Negative kvarh Pulse Output Relays (2-5)

1 to 4

1

F50

0

 

 

 

 

 

 

 

 

 

 

 

2AB5

Negative kvarh Pulse Output Interval

1 to 50000

1

F1

10

 

 

 

 

 

 

 

 

 

 

 

2AB6

Pulse Width

200 to 1000

1

F1

200

 

 

 

 

 

 

 

 

 

 

 

MONITORING / RUNNING HOUR SETUP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2AC0

Initial Generator Running Hours

0 to 999999

1

h

F12

0

 

 

 

 

 

 

 

 

 

 

 

2AC2

Generator Running Hour Alarm

0 to 2

1

F115

0

 

 

 

 

 

 

 

 

 

 

 

2AC3

Assign Alarm Relays (2-5)

1 to 4

1

F50

16

 

 

 

 

 

 

 

 

 

 

 

2AC4

Generator Running Hour Limit

1 to 1000000

1

h

F12

1000

 

 

 

 

 

 

 

 

 

 

 

2AC6

Reserved

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ANALOG INPUT/OUTPUT / ANALOG OUTPUT 1

 

 

 

 

 

 

2B00 Analog Output 1

0 to 42

1

F127

0

ANALOG INPUT/OUTPUT / ANALOG OUTPUT 2

2B01 Analog Output 2

0 to 42

1

F127

0

ANALOG INPUT/OUTPUT / ANALOG OUTPUT 3

2B02 Analog Output 3

0 to 42

1

F127

0

ANALOG INPUT/OUTPUT / ANALOG OUTPUT 4

2B03 Analog Output 4

0 to 42

1

F127

0

ANALOG INPUT/OUTPUT / ANALOG OUTPUTS

2B04

Ia Output Current Minimum

0 to 2000

1

FLA

F3

0

 

 

 

 

 

 

 

2B05

Ia Output Current Maximum

0 to 2000

1

FLA

F3

125

 

 

 

 

 

 

 

2B06

Ib Output Current Minimum

0 to 2000

1

FLA

F3

0

 

 

 

 

 

 

 

2B07

Ib Output Current Maximum

0 to 2000

1

FLA

F3

125

 

 

 

 

 

 

 

2B08

Ic Output Current Minimum

0 to 2000

1

FLA

F3

0

 

 

 

 

 

 

 

2B09

Ic Output Current Maximum

0 to 2000

1

FLA

F3

125

 

 

 

 

 

 

 

2B0A

Average Output Current Minimum

0 to 2000

1

FLA

F3

0

 

 

 

 

 

 

 

2B0B

Average Output Current Maximum

0 to 2000

1

FLA

F3

125

 

 

 

 

 

 

 

2B0C

Negative Sequence Current Minimum

0 to 2000

1

%FLA

F1

0

 

 

 

 

 

 

 

2B0D

Negative Sequence Current Maximum

0 to 2000

1

%FLA

F1

100

 

 

 

 

 

 

 

2B0E

Averaged Generator Load Minimum

0 to 2000

1

FLA

F3

0

 

 

 

 

 

 

 

1, 2, 3 See Table footnotes on page 39

34

http://www.GEindustrial.com/multilin

GE Multilin

Page 38
Image 38
GE 1601-0149-A2 manual Memory Map Sheet 24