Modbus Memory Map

 

Communications Guide

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 1: 489 Memory Map (Sheet 16 of 29)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ADDR

NAME

RANGE

STEP

UNITS

FORMAT

DEFAULT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1768

FlexCurve™ Trip Time at 12.0 PU

0 to 65535

1

ms

F1

65535

 

 

 

 

 

 

 

 

 

 

 

1769

FlexCurve™ Trip Time at 12.5 PU

0 to 65535

1

ms

F1

65535

 

 

 

 

 

 

 

 

 

 

 

176A

FlexCurve™ Trip Time at 13.0 PU

0 to 65535

1

ms

F1

65535

 

 

 

 

 

 

 

 

 

 

 

176B

FlexCurve™ Trip Time at 13.5 PU

0 to 65535

1

ms

F1

65535

 

 

 

 

 

 

 

 

 

 

 

176C

FlexCurve™ Trip Time at 14.0 PU

0 to 65535

1

ms

F1

65535

 

 

 

 

 

 

 

 

 

 

 

176D

FlexCurve™ Trip Time at 14.5 PU

0 to 65535

1

ms

F1

65535

 

 

 

 

 

 

 

 

 

 

 

176E

FlexCurve™ Trip Time at 15.0 PU

0 to 65535

1

ms

F1

65535

 

 

 

 

 

 

 

 

 

 

 

176F

FlexCurve™ Trip Time at 15.5 PU

0 to 65535

1

ms

F1

65535

 

 

 

 

 

 

 

 

 

 

 

1770

FlexCurve™ Trip Time at 16.0 PU

0 to 65535

1

ms

F1

65535

 

 

 

 

 

 

 

 

 

 

 

1771

FlexCurve™ Trip Time at 16.5 PU

0 to 65535

1

ms

F1

65535

 

 

 

 

 

 

 

 

 

 

 

1772

FlexCurve™ Trip Time at 17.0 PU

0 to 65535

1

ms

F1

65535

 

 

 

 

 

 

 

 

 

 

 

1773

FlexCurve™ Trip Time at 17.5 PU

0 to 65535

1

ms

F1

65535

 

 

 

 

 

 

 

 

 

 

 

1774

FlexCurve™ Trip Time at 18.0 PU

0 to 65535

1

ms

F1

65535

 

 

 

 

 

 

 

 

 

 

 

1775

FlexCurve™ Trip Time at 18.5 PU

0 to 65535

1

ms

F1

65535

 

 

 

 

 

 

 

 

 

 

 

1776

FlexCurve™ Trip Time at 19.0 PU

0 to 65535

1

ms

F1

65535

 

 

 

 

 

 

 

 

 

 

 

1777

FlexCurve™ Trip Time at 19.5 PU

0 to 65535

1

ms

F1

65535

 

 

 

 

 

 

 

 

 

 

 

1778

FlexCurve™ Trip Time at 20.0 PU

0 to 65535

1

ms

F1

65535

 

 

 

 

 

 

 

 

 

 

 

1779

Overcurrent Curve Multiplier

0 to 100000

1

F14

100

 

 

 

 

 

 

 

 

 

 

 

177B

Overcurrent Curve Reset

0 to 1

1

F201

0

 

 

 

 

 

 

 

 

 

 

 

CURRENT ELEMENTS / PHASE DIFFERENTIAL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

17E0

Phase Differential Trip

0 to 2

1

F115

0

 

 

 

 

 

 

 

 

 

 

 

17E1

Assign Trip Relays (1-4)

0 to 3

1

F50

1

 

 

 

 

 

 

 

 

 

 

 

17E2

Differential Trip Minimum Pickup

5 to 100

1

CT

F3

10

 

 

 

 

 

 

 

 

 

 

 

17E3

Differential Trip Slope 1

1 to 100

1

%

F1

10

 

 

 

 

 

 

 

 

 

 

 

17E4

Differential Trip Slope 2

1 to 100

1

%

F1

20

 

 

 

 

 

 

 

 

 

 

 

17E5

Differential Trip Delay

0 to 100

1

cycles

F1

0

 

 

 

 

 

 

 

 

 

 

 

CURRENT ELEMENTS / GROUND DIRECTIONAL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1800

Supervise With Digital Input

0 to 1

1

F103

1

 

 

 

 

 

 

 

 

 

 

 

1801

Ground Directional MTA

0 to 3

1

F217

0

 

 

 

 

 

 

 

 

 

 

 

1802

Ground Directional Alarm

0 to 2

1

F115

0

 

 

 

 

 

 

 

 

 

 

 

1803

Assign Alarm Relays (2-5)

1 to 4

1

F50

16

 

 

 

 

 

 

 

 

 

 

 

1804

Ground Directional Alarm Pickup

5 to 2000

1

CT

F3

5

 

 

 

 

 

 

 

 

 

 

 

1805

Ground Directional Alarm Delay

1 to 1200

1

s

F2

30

 

 

 

 

 

 

 

 

 

 

 

1806

Ground Directional Alarm Events

0 to 1

1

F105

0

 

 

 

 

 

 

 

 

 

 

 

1807

Ground Directional Trip

0 to 2

1

F115

0

 

 

 

 

 

 

 

 

 

 

 

1808

Assign Trip Relays (1-4)

0 to 3

1

F50

1

 

 

 

 

 

 

 

 

 

 

 

1809

Ground Directional Trip Pickup

5 to 2000

1

CT

F3

5

 

 

 

 

 

 

 

 

 

 

 

180A

Ground Directional Trip Delay

1 to 1200

1

s

F2

30

 

 

 

 

 

 

 

 

 

 

 

CURRENT ELEMENTS / HIGH-SET PHASE OVERCURRENT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1830

High-Set Phase Overcurrent Trip

0 to 2

1

F115

0

 

 

 

 

 

 

 

 

 

 

 

1831

Assign Trip Relays (1-4)

0 to 3

1

F50

1

 

 

 

 

 

 

 

 

 

 

 

1832

High-Set Phase Overcurrent Pickup

15 to 2000

1

CT

F3

500

 

 

 

 

 

 

 

 

 

 

 

1833

High-Set Phase Overcurrent Delay

0 to 10000

1

s

F3

100

 

 

 

 

 

 

 

 

 

 

 

VOLTAGE ELEMENTS / UNDERVOLTAGE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2000

Undervoltage Alarm

0 to 2

1

F115

0

 

 

 

 

 

 

 

 

 

 

 

2001

Assign Alarm Relays (2-5)

1 to 4

1

F50

16

 

 

 

 

 

 

 

 

 

 

 

2002

Undervoltage Alarm Pickup

50 to 99

1

Rated

F3

85

 

 

 

 

 

 

 

 

 

 

 

2003

Undervoltage Alarm Delay

2 to 1200

1

s

F2

30

 

 

 

 

 

 

 

 

 

 

 

2004

Undervoltage Alarm Events

0 to 1

1

F105

0

 

 

 

 

 

 

 

 

 

 

 

2005

Undervoltage Trip

0 to 2

1

F115

0

 

 

 

 

 

 

 

 

 

 

 

2006

Assign Trip Relays (1-4)

0 to 3

1

F50

1

 

 

 

 

 

 

 

 

 

 

 

2007

Undervoltage Trip Pickup

50 to 99

1

Rated

F3

80

 

 

 

 

 

 

 

 

 

 

 

2008

Undervoltage Trip Delay

2 to 100

1

s

F2

10

 

 

 

 

 

 

 

 

 

 

 