Modbus Memory Map
Table 1: 489 Memory Map (Sheet 9 of 29)
489
Communications Guide
| ADDR | NAME | RANGE | STEP | UNITS | FORMAT | DEFAULT | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 1138 | Clear Breaker Information | 0 to 1 | 1 | – | F103 | 0 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| SYSTEM SETUP / CURRENT SENSING | 
 | 
 | 
 | 
 | 
 | |
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 1180 | Phase CT Primary | 10 to 50001 | 1 | Amps | F1 | 50001 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 1181 | Ground CT | 0 to 3 | 1 | – | F104 | 0 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 1182 | Ground CT Ratio | 10 to 10000 | 1 | : 1 / :5 | F1 | 100 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| SYSTEM SETUP / VOLTAGE SENSING | 
 | 
 | 
 | 
 | 
 | |
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 11A0 | VT Connection Type | 0 to 2 | 1 | – | F106 | 0 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 11A1 | Voltage Transformer Ratio | 100 to 30000 | 1 | : 1 | F3 | 500 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 11A2 | Neutral VT Ratio | 100 to 24000 | 1 | : 1 | F3 | 500 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 11A3 | Neutral Voltage Transformer | 0 to 1 | 1 | – | F103 | 0 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| SYSTEM SETUP / GEN. PARAMETERS | 
 | 
 | 
 | 
 | 
 | |
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 11C0 | Generator Rated MVA | 50 to 2000001 | 1 | MVA | F13 | 2000001 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 11C2 | Generator Rated Power Factor | 5 to 100 | 1 | – | F3 | 100 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 11C3 | Generator Voltage  | 100 to 30001 | 1 | V | F1 | 30001 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 11C4 | Generator Nominal Frequency | 0 to 3 | 1 | Hz | F107 | 0 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 11C5 | Generator Phase Sequence | 0 to 2 | 1 | – | F124 | 0 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| SYSTEM SETUP / SERIAL START/STOP | 
 | 
 | 
 | 
 | 
 | |
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 11E0 | Serial Start/Stop Initiation | 0 to 1 | 1 | – | F105 | 0 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 11E1 | Startup Initiation Relays  | 1 to 4 | 1 | – | F50 | 0 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 11E2 | Shutdown Initiation Relays  | 0 to 3 | 1 | – | F50 | 0 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 11E3 | Serial Start/Stop Events | 0 to 1 | 1 | – | F105 | 0 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
DIGITAL INPUTS / BREAKER STATUS
1200 Breaker Status
0 to 1
1
–
F209
1
DIGITAL INPUTS / GENERAL INPUT A
| 1210 | Assign Digital Input | 0 to 7 | 1 | – | F210 | 0 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 1211 | Asserted Digital Input State | 0 to 1 | 1 | – | F131 | 0 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 1212 | Input Name | 0 to 12 | 1 | – | F22 | _ | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 1218 | Block Input From Online | 0 to 5000 | 1 | s | F1 | 0 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 1219 | General Input A Control | 0 to 1 | 1 | – | F105 | 0 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 121A | Pulsed Control Relay Dwell Time | 0 to 250 | 1 | s | F2 | 0 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 121B | Assign Control Relays  | 0 to 4 | 1 | – | F50 | 0 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 121C | General Input A Control Events | 0 to 1 | 1 | – | F105 | 0 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 121D | General Input A Alarm | 0 to 2 | 1 | – | F115 | 0 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 121E | Assign Alarm Relays  | 1 to 4 | 1 | – | F50 | 16 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 121F | General Input A Alarm Delay | 1 to 50000 | 1 | s | F2 | 50 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 1220 | General Input A Alarm Events | 0 to 1 | 1 | – | F105 | 0 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 1221 | General Input A Trip | 0 to 2 | 1 | – | F115 | 0 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 1222 | Assign Trip Relays  | 0 to 3 | 1 | – | F50 | 1 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 1223 | General Input A Trip Delay | 1 to 50000 | 1 | s | F2 | 50 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| DIGITAL INPUTS / GENERAL INPUT B | 
 | 
 | 
 | 
 | 
 | |
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 1230 | Assign Digital Input | 0 to 7 | 1 | – | F210 | 0 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 1231 | Asserted Digital Input State | 0 to 1 | 1 | – | F131 | 0 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 1232 | Input Name | 0 to 12 | 1 | – | F22 | _ | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 1238 | Block Input From Online | 0 to 5000 | 1 | s | F1 | 0 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 1239 | General Input B Control | 0 to 1 | 1 | – | F105 | 0 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 123A | Pulsed Control Relay Dwell Time | 0 to 250 | 1 | s | F2 | 0 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 123B | Assign Control Relays  | 0 to 4 | 1 | – | F50 | 0 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 123C | General Input B Control Events | 0 to 1 | 1 | – | F105 | 0 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 123D | General Input B Alarm | 0 to 2 | 1 | – | F115 | 0 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 123E | Assign Alarm Relays  | 1 to 4 | 1 | – | F50 | 16 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 123F | General Input B Alarm Delay | 1 to 50000 | 1 | s | F2 | 50 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 1240 | General Input B Alarm Events | 0 to 1 | 1 | – | F105 | 0 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 1241 | General Input B Trip | 0 to 2 | 1 | – | F115 | 0 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 