Modbus Memory Map
Table 1: 489 Memory Map (Sheet 9 of 29)
489
Communications Guide
ADDR | NAME | RANGE | STEP | UNITS | FORMAT | DEFAULT |
|
|
|
|
|
|
|
1138 | Clear Breaker Information | 0 to 1 | 1 | – | F103 | 0 |
|
|
|
|
|
|
|
SYSTEM SETUP / CURRENT SENSING |
|
|
|
|
| |
|
|
|
|
|
|
|
1180 | Phase CT Primary | 10 to 50001 | 1 | Amps | F1 | 50001 |
|
|
|
|
|
|
|
1181 | Ground CT | 0 to 3 | 1 | – | F104 | 0 |
|
|
|
|
|
|
|
1182 | Ground CT Ratio | 10 to 10000 | 1 | : 1 / :5 | F1 | 100 |
|
|
|
|
|
|
|
SYSTEM SETUP / VOLTAGE SENSING |
|
|
|
|
| |
|
|
|
|
|
|
|
11A0 | VT Connection Type | 0 to 2 | 1 | – | F106 | 0 |
|
|
|
|
|
|
|
11A1 | Voltage Transformer Ratio | 100 to 30000 | 1 | : 1 | F3 | 500 |
|
|
|
|
|
|
|
11A2 | Neutral VT Ratio | 100 to 24000 | 1 | : 1 | F3 | 500 |
|
|
|
|
|
|
|
11A3 | Neutral Voltage Transformer | 0 to 1 | 1 | – | F103 | 0 |
|
|
|
|
|
|
|
SYSTEM SETUP / GEN. PARAMETERS |
|
|
|
|
| |
|
|
|
|
|
|
|
11C0 | Generator Rated MVA | 50 to 2000001 | 1 | MVA | F13 | 2000001 |
|
|
|
|
|
|
|
11C2 | Generator Rated Power Factor | 5 to 100 | 1 | – | F3 | 100 |
|
|
|
|
|
|
|
11C3 | Generator Voltage | 100 to 30001 | 1 | V | F1 | 30001 |
|
|
|
|
|
|
|
11C4 | Generator Nominal Frequency | 0 to 3 | 1 | Hz | F107 | 0 |
|
|
|
|
|
|
|
11C5 | Generator Phase Sequence | 0 to 2 | 1 | – | F124 | 0 |
|
|
|
|
|
|
|
SYSTEM SETUP / SERIAL START/STOP |
|
|
|
|
| |
|
|
|
|
|
|
|
11E0 | Serial Start/Stop Initiation | 0 to 1 | 1 | – | F105 | 0 |
|
|
|
|
|
|
|
11E1 | Startup Initiation Relays | 1 to 4 | 1 | – | F50 | 0 |
|
|
|
|
|
|
|
11E2 | Shutdown Initiation Relays | 0 to 3 | 1 | – | F50 | 0 |
|
|
|
|
|
|
|
11E3 | Serial Start/Stop Events | 0 to 1 | 1 | – | F105 | 0 |
|
|
|
|
|
|
|
DIGITAL INPUTS / BREAKER STATUS
1200 Breaker Status
0 to 1
1
–
F209
1
DIGITAL INPUTS / GENERAL INPUT A
1210 | Assign Digital Input | 0 to 7 | 1 | – | F210 | 0 |
|
|
|
|
|
|
|
1211 | Asserted Digital Input State | 0 to 1 | 1 | – | F131 | 0 |
|
|
|
|
|
|
|
1212 | Input Name | 0 to 12 | 1 | – | F22 | _ |
|
|
|
|
|
|
|
1218 | Block Input From Online | 0 to 5000 | 1 | s | F1 | 0 |
|
|
|
|
|
|
|
1219 | General Input A Control | 0 to 1 | 1 | – | F105 | 0 |
|
|
|
|
|
|
|
121A | Pulsed Control Relay Dwell Time | 0 to 250 | 1 | s | F2 | 0 |
|
|
|
|
|
|
|
121B | Assign Control Relays | 0 to 4 | 1 | – | F50 | 0 |
|
|
|
|
|
|
|
121C | General Input A Control Events | 0 to 1 | 1 | – | F105 | 0 |
|
|
|
|
|
|
|
121D | General Input A Alarm | 0 to 2 | 1 | – | F115 | 0 |
|
|
|
|
|
|
|
121E | Assign Alarm Relays | 1 to 4 | 1 | – | F50 | 16 |
|
|
|
|
|
|
|
121F | General Input A Alarm Delay | 1 to 50000 | 1 | s | F2 | 50 |
|
|
|
|
|
|
|
1220 | General Input A Alarm Events | 0 to 1 | 1 | – | F105 | 0 |
|
|
|
|
|
|
|
1221 | General Input A Trip | 0 to 2 | 1 | – | F115 | 0 |
|
|
|
|
|
|
|
1222 | Assign Trip Relays | 0 to 3 | 1 | – | F50 | 1 |
|
|
|
|
|
|
|
1223 | General Input A Trip Delay | 1 to 50000 | 1 | s | F2 | 50 |
|
|
|
|
|
|
|
DIGITAL INPUTS / GENERAL INPUT B |
|
|
|
|
| |
|
|
|
|
|
|
|
1230 | Assign Digital Input | 0 to 7 | 1 | – | F210 | 0 |
|
|
|
|
|
|
|
1231 | Asserted Digital Input State | 0 to 1 | 1 | – | F131 | 0 |
|
|
|
|
|
|
|
1232 | Input Name | 0 to 12 | 1 | – | F22 | _ |
|
|
|
|
|
|
|
1238 | Block Input From Online | 0 to 5000 | 1 | s | F1 | 0 |
|
|
|
|
|
|
|
1239 | General Input B Control | 0 to 1 | 1 | – | F105 | 0 |
|
|
|
|
|
|
|
123A | Pulsed Control Relay Dwell Time | 0 to 250 | 1 | s | F2 | 0 |
|
|
|
|
|
|
|
123B | Assign Control Relays | 0 to 4 | 1 | – | F50 | 0 |
|
|
|
|
|
|
|
123C | General Input B Control Events | 0 to 1 | 1 | – | F105 | 0 |
|
|
|
|
|
|
|
123D | General Input B Alarm | 0 to 2 | 1 | – | F115 | 0 |
|
|
|
|
|
|
|
123E | Assign Alarm Relays | 1 to 4 | 1 | – | F50 | 16 |
|
|
|
|
|
|
|
123F | General Input B Alarm Delay | 1 to 50000 | 1 | s | F2 | 50 |
|
|
|
|
|
|
|
1240 | General Input B Alarm Events | 0 to 1 | 1 | – | F105 | 0 |
|
|
|
|
|
|
|
1241 | General Input B Trip | 0 to 2 | 1 | – | F115 | 0 |
|
|
|
|
|
|
|
1, 2, 3 See Table footnotes on page 39
GE Multilin |
http://www.GEindustrial.com/multilin
19 |