DNP Point Lists
DNP Point Lists
489
Communications Guide
Binary Input / Binary
Input Change (Objects
01/02)
The point list for Binary Inputs (Object 01) and Binary Input Change (Object 02) is shown below:
Table 5: Binary Inputs (Sheet 1 of 4)
| Idx | Description | Class | 
| 
 | 
 | 
 | 
| 
 | 
 | 
 | 
| 0 | Relay In Service | Class 1 | 
| 
 | 
 | 
 | 
| 1 | Trip Condition Active | Class 1 | 
| 
 | 
 | 
 | 
| 2 | Alarm Condition Active | Class 1 | 
| 
 | 
 | 
 | 
| 3 | Simulation Mode Enabled | Class 1 | 
| 
 | 
 | 
 | 
| 4 | Breaker Is Open | Class 1 | 
| 
 | 
 | 
 | 
| 5 | Breaker Is Closed | Class 1 | 
| 
 | 
 | 
 | 
| 6 | Hot Stator Fault Active | Class 1 | 
| 
 | 
 | 
 | 
| 7 | Negative Sequence Fault Active | Class 1 | 
| 
 | 
 | 
 | 
| 8 | Ground Fault Active | Class 1 | 
| 
 | 
 | 
 | 
| 9 | Loss Of Field Fault Active | Class 1 | 
| 
 | 
 | 
 | 
| 10 | VT Failure Detected | Class 1 | 
| 
 | 
 | 
 | 
| 11 | Breaker Failure Detected | Class 1 | 
| 
 | 
 | 
 | 
| 12 | Relay 1 Trip Operated | Class 1 | 
| 
 | 
 | 
 | 
| 13 | Relay 2 Auxiliary Operated | Class 1 | 
| 
 | 
 | 
 | 
| 14 | Relay 3 Auxiliary Operated | Class 1 | 
| 
 | 
 | 
 | 
| 15 | Relay 4 Auxiliary Operated | Class 1 | 
| 
 | 
 | 
 | 
| 16 | Relay 5 Alarm Operated | Class 1 | 
| 
 | 
 | 
 | 
| 17 | Relay 6 Service Operated | Class 1 | 
| 
 | 
 | 
 | 
| 18 | Setpoint Access Input Closed | Class 1 | 
| 
 | 
 | 
 | 
| 19 | Breaker Status Input Closed | Class 1 | 
| 
 | 
 | 
 | 
| 20 | Assignable Input 1 Closed | Class 1 | 
| 
 | 
 | 
 | 
| 21 | Assignable Input 2 Closed | Class 1 | 
| 
 | 
 | 
 | 
| 22 | Assignable Input 3 Closed | Class 1 | 
| 
 | 
 | 
 | 
| 23 | Assignable Input 4 Closed | Class 1 | 
| 
 | 
 | 
 | 
| 24 | Assignable Input 5 Closed | Class 1 | 
| 
 | 
 | 
 | 
| 25 | Assignable Input 6 Closed | Class 1 | 
| 
 | 
 | 
 | 
| 26 | Assignable Input 7 Closed | Class 1 | 
| 
 | 
 | 
 | 
| 27 | Trip Coil Supervision - Coil | Class 1 | 
| 
 | Detected | 
 | 
| 
 | 
 | 
 | 
| 40 | Assignable Input 1 Trip Active | Class 1 | 
| 
 | or Latched | 
 | 
| 
 | 
 | 
 | 
| 41 | Assignable Input 2 Trip Active | Class 1 | 
| 
 | or Latched | 
 | 
| 
 | 
 | 
 | 
| 42 | Assignable Input 3 Trip Active | Class 1 | 
| 
 | or Latched | 
 | 
| 
 | 
 | 
 | 
| 43 | Assignable Input 4 Trip Active | Class 1 | 
| 
 | or Latched | 
 | 
| 
 | 
 | 
 | 
| 44 | Assignable Input 5 Trip Active | Class 1 | 
| 
 | or Latched | 
 | 
| 
 | 
 | 
 | 
| 45 | Assignable Input 6 Trip Active | Class 1 | 
| 
 | or Latched | 
 | 
| 
 | 
 | 
 | 
| 46 | Assignable Input 7 Trip Active | Class 1 | 
| 
 | or Latched | 
 | 
| 
 | 
 | 
 | 
| 47 | Sequential Trip Active or | Class 1 | 
| 
 | Latched | 
 | 
| 
 | 
 | 
 | 
| 48 | Class 1 | |
| 
 | Active or Latched | 
 | 
| 
 | 
 | 
 | 
| 49 | Tachometer Trip Active or | Class 1 | 
| 
 | Latched | 
 | 
| 
 | 
 | 
 | 
Table 5: Binary Inputs (Sheet 2 of 4)
| Idx | Description | Class | 
| 
 | 
 | 
 | 
| 
 | 
 | 
 | 
| 50 | Offline Overcurrent Trip Active | Class 1 | 
| 
 | or Latched | 
 | 
| 
 | 
 | 
 | 
| 51 | Inadvertent Energization Trip | Class 1 | 
| 
 | Active or Latched | 
 | 
| 
 | 
 | 
 | 
| 52 | Phase Overcurrent Trip Active | Class 1 | 
| 
 | or Latched | 
 | 
| 
 | 
 | 
 | 
| 53 | Negative Sequence | Class 1 | 
| 
 | Overcurrent Trip Active or | 
 | 
| 
 | Latched | 
 | 
| 
 | 
 | 
 | 
| 54 | Ground Overcurrent Trip Active | Class 1 | 
| 
 | or Latched | 
 | 
| 
 | 
 | 
 | 
| 55 | Phase Differential Trip Active or | Class 1 | 
| 
 | Latched | 
 | 
| 
 | 
 | 
 | 
| 56 | Undervoltage Trip Active or | Class 1 | 
| 
 | Latched | 
 | 
| 
 | 
 | 
 | 
| 57 | Overvoltage Trip Active or | Class 1 | 
| 
 | Latched | 
 | 
| 
 | 
 | 
 | 
| 58 | Volts/Hertz Trip Active or | Class 1 | 
| 
 | Latched | 
 | 
| 
 | 
 | 
 | 
| 59 | Phase Reversal Trip Active or | Class 1 | 
| 
 | Latched | 
 | 
| 
 | 
 | 
 | 
| 60 | Underfrequency Trip Active or | Class 1 | 
| 
 | Latched | 
 | 
| 
 | 
 | 
 | 
| 61 | Overfrequency Trip Active or | Class 1 | 
| 
 | Latched | 
 | 
| 
 | 
 | 
 | 
| 62 | Neutral Overvoltage Trip Active | Class 1 | 
| 
 | or Latched | 
 | 
| 
 | 
 | 
 | 
| 63 | Neutral Undervoltage (Third | Class 1 | 
| 
 | Harmonic) Trip Active or | 
 | 
| 
 | Latched | 
 | 
| 
 | 
 | 
 | 
| 64 | Reactive Power Trip Active or | Class 1 | 
| 
 | Latched | 
 | 
| 
 | 
 | 
 | 
| 65 | Reverse Power Trip Active or | Class 1 | 
| 
 | Latched | 
 | 
| 
 | 
 | 
 | 
| 66 | Low Fwd Power Trip Active or | Class 1 | 
| 
 | Latched | 
 | 
| 
 | 
 | 
 | 
| 67 | Thermal Model Trip Active or | Class 1 | 
| 
 | Latched | 
 | 
| 
 | 
 | 
 | 
| 68 | RTD 1 Trip Active or Latched | Class 1 | 
| 
 | 
 | 
 | 
| 69 | RTD 2 Trip Active or Latched | Class 1 | 
| 
 | 
 | 
 | 
| 70 | RTD 3 Trip Active or Latched | Class 1 | 
| 
 | 
 | 
 | 
| 71 | RTD 4 Trip Active or Latched | Class 1 | 
| 
 | 
 | 
 | 
| 72 | RTD 5 Trip Active or Latched | Class 1 | 
| 
 | 
 | 
 | 
| 73 | RTD 6 Trip Active or Latched | Class 1 | 
| 
 | 
 | 
 | 
| 74 | RTD 7 Trip Active or Latched | Class 1 | 
| 
 | 
 | 
 | 
| 75 | RTD 8 Trip Active or Latched | Class 1 | 
| 
 | 
 | 
 | 
| 76 | RTD 9 Trip Active or Latched | Class 1 | 
| 
 | 
 | 
 | 
| 77 | RTD 10 Trip Active or Latched | Class 1 | 
| 
 | 
 | 
 | 
| 78 | RTD 11 Trip Active or Latched | Class 1 | 
| 
 | 
 | 
 | 
| 79 | RTD 12 Trip Active or Latched | Class 1 | 
| 
 | 
 | 
 | 
| 80 | Analog Input 1 Trip Active or | Class 1 | 
| 
 | Latched | 
 | 
| 
 | 
 | 
 | 
| 81 | Analog Input 2 Trip Active or | Class 1 | 
| 
 | Latched | 
 | 
| 
 | 
 | 
 | 
| GE Multilin | 
http://www.GEindustrial.com/multilin
| 49 | 