DNP Point Lists
Table 8: Analog Inputs Point List (Sheet 3 of 4)
489
Communications Guide
INDEX | FOR- | DESCRIPTION | EVENT CLASS | NOTES |
| MAT |
| ASSIGNED TO |
|
|
|
|
|
|
|
|
|
|
|
74 | F1 | Third Harmonic Neutral Voltage (volts) | Class 2 | Note 10 |
|
|
|
|
|
75 | F10 | Third Harmonic Neutral Voltage (tenths of | Class 2 | Note 10 |
|
| a volt) |
|
|
|
|
|
|
|
76 | F1 | Third Harmonic Terminal Voltage (volts) | Class 2 | Note 10 |
|
|
|
|
|
77 | F10 | Third Harmonic Terminal Voltage (tenths of | Class 2 | Note 10 |
|
| a volt) |
|
|
|
|
|
|
|
78 | F2 | Vab/Iab (loss of excitation impedance) | Class 2 |
|
|
|
|
|
|
79 | F1 | Vab/Iab Angle (loss of excitation | Class 2 |
|
|
| impedance angle) |
|
|
|
|
|
|
|
80 | F6 | Power Factor | Class 2 |
|
|
|
|
|
|
81 | F1 | Real Power (MW) | Class 2 | Note 8 |
|
|
|
|
|
82 | F1 | Real Power (kW) | Class 2 | Note 8 |
|
|
|
|
|
83 | F1 | Reactive Power (Mar) | Class 2 | Note 8 |
|
|
|
|
|
84 | F1 | Reactive Power (kvar) | Class 2 | Note 8 |
|
|
|
|
|
85 | F1 | Apparent Power (MVA) | Class 2 | Note 8 |
|
|
|
|
|
86 | F1 | Apparent Power (kVA) | Class 2 | Note 8 |
|
|
|
|
|
87 | F1 | Hottest Stator RTD | Class 2 | Note 3 |
|
|
|
|
|
88 | F4 | Hottest Stator RTD Temperature (°C) | Class 2 |
|
|
|
|
|
|
89 | F4 | RTD #1 Temperature (°C) | Class 2 |
|
|
|
|
|
|
90 | F4 | RTD #2 Temperature (°C) | Class 2 |
|
|
|
|
|
|
91 | F4 | RTD #3 Temperature (°C) | Class 2 |
|
|
|
|
|
|
92 | F4 | RTD #4 Temperature (°C) | Class 2 |
|
|
|
|
|
|
93 | F4 | RTD #5 Temperature (°C) | Class 2 |
|
|
|
|
|
|
94 | F4 | RTD #6 Temperature (°C) | Class 2 |
|
|
|
|
|
|
95 | F4 | RTD #7 Temperature (°C) | Class 2 |
|
|
|
|
|
|
96 | F4 | RTD #8 Temperature (°C) | Class 2 |
|
|
|
|
|
|
97 | F4 | RTD #9 Temperature (°C) | Class 2 |
|
|
|
|
|
|
98 | F4 | RTD #10 Temperature (°C) | Class 2 |
|
|
|
|
|
|
99 | F4 | RTD #11 Temperature (°C) | Class 2 |
|
|
|
|
|
|
100 | F4 | RTD #12 Temperature (°C) | Class 2 |
|
|
|
|
|
|
101 | F1 | Current Demand | Class 2 | Note 7 |
|
|
|
|
|
102 | F1 | MW Demand | Class 2 | Note 8 |
|
|
|
|
|
103 | F1 | kW Demand | Class 2 | Note 8 |
|
|
|
|
|
104 | F1 | Mvar Demand | Class 2 | Note 8 |
|
|
|
|
|
105 | F1 | kvar Demand | Class 2 | Note 8 |
|
|
|
|
|
106 | F1 | MVA Demand | Class 2 | Note 8 |
|
|
|
|
|
107 | F1 | kVA Demand | Class 2 | Note 8 |
|
|
|
|
|
108 | F1 | Peak Current Demand | Class 2 | Note 7 |
|
|
|
|
|
109 | F1 | Peak MW Demand | Class 2 | Note 8 |
|
|
|
|
|
110 | F1 | Peak kW Demand | Class 2 | Note 8 |
|
|
|
|
|
111 | F1 | Peak Mvar Demand | Class 2 | Note 8 |
|
|
|
|
|
112 | F1 | Peak kvar Demand | Class 2 | Note 8 |
|
|
|
|
|
113 | F1 | Peak MVA Demand | Class 2 | Note 8 |
|
|
|
|
|
114 | F1 | Peak kVA Demand | Class 2 | Note 8 |
|
|
|
|
|
115 | F12 | Analog Input 1 | Class 2 | Note 9 |
|
|
|
|
|
116 | F12 | Analog Input 2 | Class 2 | Note 9 |
|
|
|
|
|
117 | F12 | Analog Input 3 | Class 2 | Note 9 |
|
|
|
|
|
118 | F12 | Analog Input 4 | Class 2 | Note 9 |
|
|
|
|
|
119 | F1 | Tachometer RPM | Class 2 |
|
|
|
|
|
|
120 | F1 | Average Generator Load | Class 2 |
|
|
|
|
|
|
GE Multilin |
http://www.GEindustrial.com/multilin
55 |