489

 

 

 

 

Modbus Memory Map

 

Communications Guide

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 1: 489 Memory Map (Sheet 14 of 29)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ADDR

NAME

RANGE

STEP

UNITS

FORMAT

DEFAULT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1643

FlexCurve™ Trip Time at 11.5 PU

0 to 65535

1

ms

F1

65535

 

 

 

 

 

 

 

 

 

 

 

1644

FlexCurve™ Trip Time at 12.0 PU

0 to 65535

1

ms

F1

65535

 

 

 

 

 

 

 

 

 

 

 

1645

FlexCurve™ Trip Time at 12.5 PU

0 to 65535

1

ms

F1

65535

 

 

 

 

 

 

 

 

 

 

 

1646

FlexCurve™ Trip Time at 13.0 PU

0 to 65535

1

ms

F1

65535

 

 

 

 

 

 

 

 

 

 

 

1647

FlexCurve™ Trip Time at 13.5 PU

0 to 65535

1

ms

F1

65535

 

 

 

 

 

 

 

 

 

 

 

1648

FlexCurve™ Trip Time at 14.0 PU

0 to 65535

1

ms

F1

65535

 

 

 

 

 

 

 

 

 

 

 

1649

FlexCurve™ Trip Time at 14.5 PU

0 to 65535

1

ms

F1

65535

 

 

 

 

 

 

 

 

 

 

 

164A

FlexCurve™ Trip Time at 15.0 PU

0 to 65535

1

ms

F1

65535

 

 

 

 

 

 

 

 

 

 

 

164B

FlexCurve™ Trip Time at 15.5 PU

0 to 65535

1

ms

F1

65535

 

 

 

 

 

 

 

 

 

 

 

164C

FlexCurve™ Trip Time at 16.0 PU

0 to 65535

1

ms

F1

65535

 

 

 

 

 

 

 

 

 

 

 

164D

FlexCurve™ Trip Time at 16.5 PU

0 to 65535

1

ms

F1

65535

 

 

 

 

 

 

 

 

 

 

 

164E

FlexCurve™ Trip Time at 17.0 PU

0 to 65535

1

ms

F1

65535

 

 

 

 

 

 

 

 

 

 

 

164F

FlexCurve™ Trip Time at 17.5 PU

0 to 65535

1

ms

F1

65535

 

 

 

 

 

 

 

 

 

 

 

1650

FlexCurve™ Trip Time at 18.0 PU

0 to 65535

1

ms

F1

65535

 

 

 

 

 

 

 

 

 

 

 

1651

FlexCurve™ Trip Time at 18.5 PU

0 to 65535

1

ms

F1

65535

 

 

 

 

 

 

 

 

 

 

 

1652

FlexCurve™ Trip Time at 19.0 PU

0 to 65535

1

ms

F1

65535

 

 

 

 

 

 

 

 

 

 

 

1653

FlexCurve™ Trip Time at 19.5 PU

0 to 65535

1

ms

F1

65535

 

 

 

 

 

 

 

 

 

 

 

1654

FlexCurve™ Trip Time at 20.0 PU

0 to 65535

1

ms

F1

65535

 

 

 

 

 

 

 

 

 

 

 

1655

Overcurrent Curve Multiplier

0 to 100000

1

F14

100

 

 

 

 

 

 

 

 

 

 

 

1657

Overcurrent Curve Reset

0 to 1

1

F201

0

 

 

 

 

 

 

 

 

 

 

 

1658

Voltage Lower Limit

10 to 60

1

%

F1

10

 

 

 

 

 

 

 

 

 

 

 

CURRENT ELEMENTS / NEGATIVE SEQUENCE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1700

Negative Sequence Alarm

0 to 2

1

F115

0

 

 

 

 

 

 

 

 

 

 

 

1701

Assign Alarm Relays (2-5)

1 to 4

1

F50

16

 

 

 

 

 

 

 

 

 

 

 

1702

Negative Sequence Alarm Pickup

3 to 100

1

%FLA

F1

3

 

 

 

 

 

 

 

 

 

 

 

1703

Negative Sequence Alarm Delay

1 to 1000

1

s

F2

50

 

 

 

 

 

 

 

 

 

 

 

1704

Negative Sequence Alarm Events

0 to 1

1

F105

0

 

 

 

 

 

 

 

 

 

 

 

1705

Negative Sequence Overcurrent Trip

0 to 2

1

F115

0

 

 

 

 

 

 

 

 

 

 

 

1706

Assign Trip Relays (1-4)

0 to 3

1

F50

1

 

 

 

 

 

 

 

 

 

 

 

1707

Negative Sequence Overcurrent Trip Pickup

3 to 100

1

%FLA

F1

8

 

 

 

 

 

 

 

 

 

 

 

1708

Negative Sequence Overcurrent Constant K

1 to 100

1

F1

1

 

 

 

 

 

 

 

 

 

 

 

1709

Negative Sequence Overcurrent Maximum Time

10 to 1000

1

s

F1

1000

 

 

 

 

 

 

 

 

 

 

 

170A

Negative Sequence Overcurrent Reset Rate

0 to 9999

1

s

F2

2270

 

 

 

 

 

 

 

 

 

 

 

CURRENT ELEMENTS / GROUND O/C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1720

Ground Overcurrent Alarm

0 to 2

1

F115

0

 

 

 

 

 

 

 

 

 

 

 

1721

Assign Alarm Relays (2-5)

1 to 4

1

F50

16

 

 

 

 

 

 

 

 

 

 

 

1722

Ground Overcurrent Alarm Pickup

5 to 2000

1

CT

F3

20

 

 

 

 

 

 

 

 

 

 

 

1723

Ground Overcurrent Alarm Delay

0 to 100

1

Cycles

F1

0

 

 

 

 

 

 

 

 

 

 

 

1724

Ground Overcurrent Alarm Events

0 to 1

1

F105

0

 

 

 

 

 

 

 

 

 

 

 

1725

Ground Overcurrent Trip

0 to 2

1

F115

0

 

 

 

 

 

 

 

 

 

 

 

1726

Assign Trip Relays (1-4)

0 to 3

1

F50

1

 

 

 

 

 

 

 

 

 

 

 

1727

Ground Overcurrent Trip Pickup

5 to 2000

1

CT

F3

20

 

 

 

 

 

 

 

 

 

 

 

1728

Curve Shape

0 to 13

1

F128

0

 

 

 

 

 

 

 

 

 

 

 

1729

FlexCurve™ Trip Time at 1.03 PU

0 to 65535

1

ms

F1

65535

 

 

 

 

 

 

 

 

 

 

 

172A

FlexCurve™ Trip Time at 1.05 PU

0 to 65535

1

ms

F1

65535

 

 

 

 

 

 

 

 

 

 

 

172B

FlexCurve™ Trip Time at 1.10 PU

0 to 65535

1

ms

F1

65535

 

 

 

 

 

 

 

 

 

 

 

172C

FlexCurve™ Trip Time at 1.20 PU

0 to 65535

1

ms

F1

65535

 

 

 

 

 

 

 

 

 

 

 

172D

FlexCurve™ Trip Time at 1.30 PU

0 to 65535

1

ms

F1

65535

 

 

 

 

 

 

 

 

 

 

 

172E

FlexCurve™ Trip Time at 1.40 PU

0 to 65535

1

ms

F1

65535

 

 

 

 

 

 

 

 

 

 

 

172F

FlexCurve™ Trip Time at 1.50 PU

0 to 65535

1

ms

F1

65535

 

 

 

 

 

 

 

 

 

 

 

1730

FlexCurve™ Trip Time at 1.60 PU

0 to 65535

1

ms

F1

65535

 

 

 

 

 

 

 

 

 

 

 

1731

FlexCurve™ Trip Time at 1.70 PU

0 to 65535

1

ms

F1

65535

 

 

 

 

 

 

 

 

 

 

 

1732

FlexCurve™ Trip Time at 1.80 PU

0 to 65535

1

ms

F1

65535

 

 

 

 

 

 

 

 

 

 

 

1, 2, 3 See Table footnotes on page 39

24

http://www.GEindustrial.com/multilin

GE Multilin

Page 28
Image 28
GE 1601-0149-A2 manual Memory Map Sheet 14, Current Elements / Negative Sequence, Current Elements / Ground O/C