Greenheck Fan 470656 manual Installation of Two Pipe Venting – Horizontal, Install Exhaust Pipe

Models: 470656

1 72
Download 72 pages 41.99 Kb
Page 13
Image 13
Installation of Two Pipe Venting – Horizontal

Installation of Two Pipe Venting – Horizontal

Refer to the diagram below for venting on horizontal concentric systems. Maintain at least 12 inches of clearance between the exhaust pipe termination and the exterior surface of the exterior wall (Dim. A).

The combustion air pipe must be a minimum of 12 inches from the exhaust pipe and 24 inches from the exterior surface of the outside wall (Dim. B).

A minimum of 1 inch and a maximum of 48 inches of building wall thickness is required for separated combustion vent pipe.

A = 12 inch minimum

 

B = 24 inch minimum

Exterior

C = 12 inch minimum

Wall

 

 

 

Exhaust

 

 

Vent

 

 

Terminal

 

 

B

 

 

A

 

EXHAUST

 

 

 

C

Pitch vent pipe

COMBUSTION AIR

 

downward

 

 

 

from furnace

 

 

¼ inch per foot

Two (2) field-supplied

 

 

support brackets

 

 

 

Combustion

 

 

Air Inlet

 

 

Terminal

Vent Connection Diameter

Vent terminals must be used. The optional vent kit includes two terminals. Construct the vent system as shown in the drawings and refer to the table for the correct vent connection diameters.

Furnace Size

Exhaust

Combustion

(MBH)

(inches)

(inches)

 

 

 

75 - 175

4

4

 

 

 

200 - 400

6

6

 

 

 

Vent Length

Refer to table for minimum and maximum vent lengths. The minimum vent length is 5 feet and the maximum vent length is 50 feet. The total equivalent vent length must include elbows. The equivalent length of a 4 inch elbow is 6 feet and the equivalent length of a 6 inch elbow is 10 feet.

Vent

Minimum

Maximum

Length

(feet)

(feet)

 

 

 

Horizontal

5

50

 

 

 

1. Install Exhaust Pipe

Run an exhaust pipe from the unit’s combustion exhaust through the exterior wall to the outdoors. The exhaust pipe must terminate at least 12 inches from the outside surface of the outside wall. Attach exhaust vent terminal to the end of the exhaust pipe. Using field-supplied mounting brackets, support the exhaust pipe as needed.

®

2. Install Combustion Air Pipe

Run a combustion air pipe from the unit’s combustion air intake through the exterior wall to the outdoors. The combustion air pipe must terminate at least 12 inches from the combustion vent pipe and 24 inches from the exterior surface of the outside wall. Attach the combustion air inlet guard to the end of the combustion air pipe. Using field-supplied mounting brackets, support the combustion air pipe as needed.

3. Seal Wall Openings

Using an appropriate method, seal the wall openings around the piping.

INTAKE END

Exhaust Connection

Exhaust Connection

(Model IGX)

(Model IG)

DISCHARGE

END

Combustion Air Connection

Combustion Air Connection

(Model IGX)

(Model IG)

Model IG / IGX Make-Up Air 13

Page 13
Image 13
Greenheck Fan 470656 Installation of Two Pipe Venting – Horizontal, Install Exhaust Pipe, Install Combustion Air Pipe