Troubleshooting
Single or 2:1 Stage Furnace Will Not Light
24 VAC across R and X?
Yes
24 VAC across W1 and X?
Yes
24 VAC across 22 and 21?
Yes
24 VAC across 24 VAC and
21 on SC1 controller?
Yes
24 VAC across A and 21?
Yes
High limit (HLC1) open?
No
Ignition controller (IC#) red LED
blinks 7 times or is on
No
Ignition controller (IC#) red LED
blinks 6 times
No
Ignition controller (IC#) red LED blinks
1 time, 2 times or 4 times
Yes
Everything is working
properly, consult factory.
No
No
No
No
No
Yes
Yes
Yes
Yes
Main disconnect (DS1) open or defective
Close, repair or replace
Main transformer (TR1) fault
Replace main transformer
Heat Switch (S4) open
(Turn Heat Switch (S4) on)
Heating Transformer (TR2) Fault
Replace heating transformer
Optional inlet air sensor (TS4) open
Adjust setting. Reference Blower
Heat relay (RH) is not energized
Check for loose connections. Repair or replace heat relay (RH)
Discharge air selector (TS2) improperly set or faulty
Adjust setting (see Staged
Furnace stage one contact (SC1) defective (stage only)
Replace furnace stage one contact
Discharge temperature was above high limit setting.
Wait for high limit to cool and reset.
Ignition controller (IC1) failed.
(Replace ignition controller)
Combustion blower (CM) not functioning
Replace combustion blower or relay (CR)
Air proving switch (PS2) defective.
Replace air proving switch
Improper manifold pressure
Set high and low manifold pressure (refer to Single Stage or
2:1 Staged Control
Faulty spark rod or spark gap does not equal 1/8 inch
Replace spark rod or adjust gap to 1⁄8 inch
50 Model IG / IGX
®