Sequence of Operation

8:1 Staged Control

1.Exhaust Fan Contact (S1) Manually Closed (optional)

Power passes through N.C. contact on exhaust fan overload (ST2 OL), which is closed if exhaust fan (M2) has not overloaded

Power passes to exhaust fan starter (ST2)

N.O. contact on exhaust fan starter (ST2) is energized and closed

Power passes to and energizes exhaust fan (M2)

2. Supply Fan Contact (S2) Manually Closed

Power passes through N.C. field-supplied fire contact (FSC)

Power passes through optional N.O. contact on exhaust fan starter (ST2), which is closed when the optional exhaust starter (ST2) is activated

Power passes through N.C. contact on supply starter overload (ST1 OL), which is closed if the supply fan has not overloaded

Power passes through N.C. contact on optional freeze protection timer (RT4), which is closed if the temperature has remained above the set point

Power passes to and energizes optional inlet damper (D1), which opens

Power passes through optional damper limit switch

(DL1), which is energized and closed if the optional inlet damper is open. It may take several minutes for the damper to fully open and for the damper limit switch to close

Power passes to and energizes fan relay (RF)

Power passes through N.O. contact on fan relay

(RF), which is closed once the fan relay (RF) is activated

Power passes to and energizes starter relay (ST1)

N.O. contact on supply fan starter (ST1) is energized and closed

Supply fan (M1) starts

3. Heat Contact (S4) Manually Closed

Power passes through N.O. contact on fan relay

(RF), which is energized and closed if the supply fan (M1) is on

Power passes to and energizes the heat relay (RH)

N.O. contact on heat relay (RH) closes

The stage controller (SC1) compares the inlet air temperature to the inlet air set point (iAS, FX Program Menu). If the inlet air temperature is below the discharge air setting (dtS, FX Program Menu), the stage controller sends a call for heat to the ignition controller (IC1)

4. Ignition Controller (IC1) Sequence of Operation

The N.O. contact on air proving switch (PS2) is open

The stage controller (SC1) energizes the combustion blower relay (CR)

N.O. contact on combustion blower relay (CR) closes

Power passes to and energizes the combustion blower (CM)

The N.O. contact on air proving switch (PS2) closes

Power passes to and energizes air proving switch relay (R9)

N.O. contacts on air proving switch (R9) closes

The ignition controller (IC) completes a 30 second pre-purge

The main gas valve (MV) fully opens (100%)

Igniter begins sparking

10 second trial for ignition begins

The furnace will light

The stage controller (SC1) will choose which stage to light the furnace at based on the discharge air temperature setting (dtS, FX Program Menu) and the outside air temperature (TS1)

When the flame is detected, the igniter stops sparking

The furnace will remain at high fire (100%) for 20 seconds

The stage controller (SC1) will stage the main gas valves (MV#) as needed between low fire, high fire and off

If the furnace is at low fire and the discharge temperature sensor (TS2) reading remains above the discharge air temperature setting (dtS, FX Program Menu) for more than six minutes, the furnace will shut down

5. Staging Control Sequence of Operation

If the discharge temperature (TS2) is below the discharge air temperature set point (dtS, FX Program Menu), the furnace will stage up

If the discharge temperature (TS2) is above the discharge air temperature set point (dtS, FX Program Menu), the furnace will stage down

If the discharge temperature (TS2) is above the discharge air temperature set point (dtS, FX Program Menu) and the furnace is at low fire, the furnace will shut off

If the furnace is at high fire and the discharge air temperature setting (dtS, FX Program Menu) is not satisfied, the furnace will remain at high fire

If the furnace is at low fire and the discharge air temperature setting (dtS, FX Program Menu) is satisfied, the furnace will shut off

6.Optional Evaporative Cooling Contact (S4) Closed*

N.O. contact on fan relay (RF) is energized and closed

Power passes through N.O. contact on optional inlet air sensor (TS4), which is energized and closed if the inlet air temperature is above the set point

Power passes to and energizes cool relay (RC)

®

Model IG / IGX Make-Up Air 43

Page 43
Image 43
Greenheck Fan 470656 manual Sequence of Operation Staged Control, Staging Control Sequence of Operation