Troubleshooting

8:1 Staged Furnace Will Not Light

... continued from

 

 

previous page.

 

 

 

 

 

 

 

 

 

With the combustion blower

 

 

(CM) on for at least

No

 

30 seconds, is there

 

 

 

24 VAC across T and A or E?

 

 

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

Ignition controller (IC#)

Yes

 

red LED

 

 

 

blinks 7 times or is on

 

 

 

 

 

 

 

 

 

No

 

 

 

 

 

 

Ignition controller (IC#)

Yes

 

red LED blinks

 

 

 

1 time, 2 times or 4 times

 

 

 

 

 

 

 

 

 

No

 

 

 

 

 

 

Cycle power to the unit

 

 

and wait 30 seconds

 

 

 

 

 

 

 

 

 

 

Does the combustion relay

No

 

 

(R9 or CR) close?

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

Does the combustion

No

 

blower (CM) run?

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

Does the combustion

Yes

 

blower stop after

 

 

 

30 seconds of operation?

 

 

 

 

 

 

 

 

 

No

 

 

 

 

 

 

Everything is working properly,

 

 

consult factory.

 

 

 

 

 

 

Furnace controller (SC1) defective

Replace furnace controller (SC1)

Ignition controller(s) (IC#) failed

Replace faulty ignition controller(s)

Improper manifold pressure

Set high and low manifold pressure (refer to 8:1 Staged Start-Up section)

Faulty spark rod or spark gap does not equal 1/8 inch

Replace spark rod or adjust gap to 18 inch

Internal high limit tripped (temperature above set point)

Let temperatures cool

Internal inlet air sensor open

Adjust inlet air sensor setting (refer to 8:1 Staged Start-Up section)

Combustion relay (R9 or CR) defective

Replace defective combustion relay (R9 or CR)

Combustion blower fuse (FU9) blown

Replace combustion blower fuse (FU9)

Combustion blower (CM) defective

Replace defective combustion blower (CM)

Airflow switch (PS2) defective

Replace defective airflow switch (PS2)

Airflow relay (R9) defective

Replace defective airflow relay (R9)

®

Model IG / IGX Make-Up Air 55

Page 55
Image 55