Greenheck Fan 470656 8:1 Staged Control, continued, Operation and Errors Ignition Controller

Models: 470656

1 72
Download 72 pages 41.99 Kb
Page 44
Image 44
8:1 Staged Control, continued

Sequence of Operation

8:1 Staged Control, continued

N.O. contact on cool relay (RC) is energized and closed

Power passes to evaporative cooling pump (P1)

*If DX or chilled water coils are used rather than an evaporative cooler, the cooling sequence of operation will depend on the coil controls. Cooling coil controls are supplied by others.

44Model IG / IGX Make-Up Air

Operation and Errors -

Ignition Controller

NOTE

The green LED light indicates NORMAL operation while the red LED light indicates an ERROR operation.

This controller is found only in the furnace control center. It has an LED indicator light on the top right of the controller that

will flash GREEN for NORMAL operation or RED for an ERROR. Some furnace configurations have two of these controllers.

The following are the green LED codes of operation:

GREEN LED Indications - NORMAL OPERATION

Flash Code

Flash Code Indication

 

 

Steady on

Flame detected, main burner on

 

 

0.1 second on/off

Controller is sparking

 

 

0.5 second on/off

Purge or inter-purge time

 

 

0.5 second on/4.5 second off

Retry or recycle time

 

 

The following are the red LED codes of error:

RED LED Indications - ERROR OPERATION

Flash Code

Flash Code Indication

 

 

Blinks 1 time

No flame in trial time error

 

 

Blinks 2 times

Flame sense circuit error

 

 

Blinks 3 times

Valve circuit error

 

 

Blinks 4 times

Flame loss error

 

 

Blinks 6 times

Airflow error

 

 

Blinks 7 times

Ground or internal error

 

 

Steady on

Line voltage/frequency error

 

 

®