Greenheck Fan 470656 Sequence of Operation 2:1 Staged Sequence, Heat Contact S4 Manually Closed

Models: 470656

1 72
Download 72 pages 41.99 Kb
Page 38
Image 38
Sequence of Operation

Sequence of Operation

2:1 Staged Sequence

1.Exhaust Fan Contact (S1) Manually Closed (optional)

Power passes through N.C. contact on exhaust fan overload (ST2 OL), which is closed if exhaust fan (M2) has not overloaded

Power passes to exhaust fan starter (ST2)

N.O. contact on exhaust fan starter (ST2) is energized and closed

Power passes to and energizes exhaust fan (M2)

2. Supply Fan Contact (S2) Manually Closed

Power passes through N.C. field-supplied fire contact (FSC)

Power passes through optional N.O. contact on exhaust fan starter (ST2), which is closed when the optional exhaust starter (ST2) is activated

Power passes through N.C. contact on supply starter overload (ST1 OL), which is closed if the supply fan has not overloaded

Power passes through N.C. contact on optional freeze protection timer (RT4), which is closed if the temperature has remained above the set point

Power passes to and energizes optional inlet damper (D1), which opens

Power passes through optional damper limit switch

(DL1), which is energized and closed if the optional inlet damper is open. It may take several minutes for the damper to fully open and for the damper limit switch to close

Power passes to and energizes fan relay (RF)

Power passes through N.O. contact on fan relay

(RF), which is closed once the fan relay (RF) is activated

Power passes to and energizes starter relay (ST1)

N.O. contact on supply fan starter (ST1) is energized and closed

Supply fan (M1) starts

3. Heat Contact (S4) Manually Closed

Power passes through N.O. fan relay (RF), which is energized and closed if the supply fan (M1) is on

Power passes through N.C. contact on optional inlet air sensor (TS4), which is closed if inlet air temperature is below the set point

Power passes to and energizes the heat relay (RH)

N.O. contact on heat relay (RH) closes

24 VAC is supplied to stage controller (SC1)

If the discharge temperature is less than the set point on the discharge air sensor (TS2) and the high temperature limit control (HLC1) has not been tripped, the N.O. contact for furnace stage controller will close

Power will be supplied to the ignition controller

(IC1), which will begin its sequence of operation

4. Ignition Controller (IC1) Sequence of Operation

The N.O. contact on air proving switch (PS2) is open

The ignition controller (IC1) energizes the combustion blower relay (CR)

N.O. contact on combustion blower relay (CR) closes

Power passes to and energizes the combustion blower (CM)

The N.O. contact on air proving switch (PS2) closes

The ignition controller (IC1) begins a 15 second pre-purge

The high fire relay (RT3) is energized and the N.O. contact on high fire relay (RT3) closes

The main gas valve (MV) fully opens (100%)

Igniter begins sparking

10 second trial for ignition begins

The furnace will light at high fire (100%)

When the flame is detected, the igniter stops sparking

The furnace will remain at high fire (100%) for at least 10 seconds

High fire contact (RT3) will open

Furnace stages to maintain the discharge air temperature set point (SC1)

5. High Fire – Low Fire Sequence of Operation

The furnace lights at high fire (100%) and remains at high fire for 10 seconds

If the discharge temperature is above the discharge air sensor (TS2) set point, the N.O. furnace stage 2 controller contact (SC2), will open and the furnace will go to low fire (50%)

If the furnace is at low fire (50%) and the discharge temperature is above the discharge air sensor (TS2) set point, the furnace stage 1 contact (SC1) will open and the furnace will shut down

If the furnace is at low fire (50%) and the discharge temperature is below the discharge air sensor (TS2) set point, the furnace stage 2 contact (SC2) will close and the furnace will go to high fire

6.Optional Evaporative Cooling Contact (S4) Closed*

N.O. contact on fan relay (RF) is energized and closed

Power passes through N.O. contact on optional inlet air sensor (TS4), which is energized and closed if the inlet air temperature is above the set point

Power passes to and energizes cool relay (RC)

N.O. contact on cool relay (RC) is energized and closed

Power passes to evaporative cooling pump (P1)

*If DX or chilled water coils are used rather than an evaporative cooler, the cooling sequence of operation will depend on the coil controls. Cooling coil controls are supplied by others.

38 Model IG / IGX Make-Up Air

®

Page 38
Image 38
Greenheck Fan 470656 manual Sequence of Operation 2:1 Staged Sequence, Exhaust Fan Contact S1 Manually Closed optional