Greenheck Fan 470656 Reference - Model IGX 2:1 Modulation, Reference - Model IGX 4:1 Modulation

Models: 470656

1 72
Download 72 pages 41.99 Kb
Page 69
Image 69
Reference - Model IGX (2:1 Modulation)

Reference - Model IGX (2:1 Modulation)

Reference - Model IGX (4:1 Modulation)

5

1

 

6

 

4

2

3

 

7

 

9

8

Manifold

Gas Pressure

Test Port

Modulating

Staged

Gas Valve

Gas Valve

3/4 inch Gas Supply Reference - Model IGX (4:1 Modulation) Connection

6 10

9

3

1

2

 

7

 

4

 

5

 

 

8

 

 

 

11

 

 

11

Manifold

Gas Pressure

Test Port

Modulating

Staged

Gas Valve

Gas Valve

3/4 inch Gas Supply Modulating Connection

note

This is a typical furnace control center, the control center in your unit may be different. Reference the ladder diagram on the inside of the control center door for a unit specific wiring diagram.

1.Low Voltage Transformer - Provides low voltage to the ignition controller and amplifier.

2.Control Terminal Block - Provides wiring access to heat controls.

3.Control Terminal Block - Provides wiring access to heat controls.

4.Ignition Controller - Controls the ignition of the furnace. Maintains safe operation of the furnace.

5.Amplifier - Controls the modulating valve based on the input from the temperature selector and the discharge air sensor.

6.Temperature Selector - Allows the user to adjust discharge air temperature.

7.Combustion Blower Contact - Passes power to the combustion blower.

8.Airflow Switch - Monitors the airflow inside the heat exchanger to ensure proper combustion airflow.

9.High Fire Relay - Allows furnace to ignite on high fire.

®

note

This is a typical furnace control center, the control center in your unit may be different. Reference the ladder diagram on the inside of the control center door for a unit specific wiring diagram.

1.Low Voltage Transformer - Provides low voltage to the ignition controller.

2.Low Voltage Transformer - Provides low voltage to the 4:1 electronic modulation controller.

3.Low Voltage Transformer - Provides low voltage to the amplifier.

4.Control Terminal Block - Provides wiring access to controls.

5.Control Terminal Block - Provides wiring access to controls.

6.Input Converter - Receives and converts signal from Building Management System (BMS).

7.Ignition Controllers - Controls the ignition of the furnace. Maintains safe operation of the furnace.

8.Modulation Controller - Provides 4:1 modulation turndown control of furnace based on the discharge air temperature.

9.Amplifier - Controls the modulating valve based on the input from the modulation controller settings and discharge air temperature sensor reading.

10.Combustion Blower Relay - Passes power to the variable speed combustion blower.

11.Airflow Switches - Monitors the airflow inside the heat exchanger to ensure proper combustion airflow.

Model IG / IGX Make-Up Air 69

Page 69
Image 69
Greenheck Fan 470656 manual Reference - Model IGX 2:1 Modulation, Reference - Model IGX 4:1 Modulation, Modulating, Staged