Note
The most accurate way to measure the air volume is by using a pitot traverse method downstream of the blower. Other methods can be used but should be proven and accurate.
Important
Changing the air volume can significantly increase the motor’s amps. If the air volume is changed, the motor’s amps must be checked to prevent overloading the motor.
Note
To ensure accuracy, the dampers are to be open when measuring the air volume.
6. Set-up Optional Components
Adjust the settings on the optional components. See the Control Center Layout in the Reference section for location of optional components.
•Heating Inlet Air Sensor
Typical setting:
•Cooling Inlet Air Sensor
Typical setting: 75ºF
•Building Freeze Protection
Typical setting: 5 minutes; 45ºF
•Dirty Filter Gauge
Typical setting: Settings vary greatly for each unit. See Reference section for adjusting information.
Note
If your unit is equipped with a 4:1 modulation or 8:1 staged control, the inlet air sensor and building freeze protection may be included in the furnace controller. If this is the case, instructions for setting the inlet air sensor and building freeze protection are included in the Furnace
24 Model IG / IGX
®