Troubleshooting

8:1 Staged Furnace Will Not Light

24 VAC across R and X?

No

 

 

 

 

 

 

 

 

Yes

 

 

 

No

 

 

 

 

24 VAC across W1 and X?

 

 

 

 

 

 

 

 

 

 

 

 

Yes

 

 

 

 

No

 

24 VAC across 22 and 21?

 

 

 

 

 

 

 

Yes

N.O. contact on heat relay (RH)

No

 

closed?

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

DT1 displayed on furnace

Yes

 

controller (SC1)?

 

 

 

 

 

 

 

No

 

 

 

 

 

 

OT1 displayed on furnace

Yes

 

controller (SC1)?

 

 

 

 

 

 

 

No

 

 

 

 

 

 

Blank screen on furnace

Yes

 

controller (SC1)?

 

 

 

 

 

 

 

No

 

 

 

 

 

 

 

 

 

 

24 VAC across terminals

No

 

 

S and T?

 

 

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

With the combustion blower

Yes

 

(CM) off, is the N.O.

 

 

 

airflow switch (PS2) closed?

 

 

 

 

 

No

 

 

 

 

 

 

 

 

 

 

Continues on next page...

 

 

 

 

 

 

Main disconnect (DS1) open or defective

Close, repair or replace

Main transformer (TR1) fault

Replace main transformer

Heat switch (S4) open or not wired

Close or replace heat switch (S4)

Heat transformer (TR2) fault

Replace heating transformer

Heat relay (RH) is not energized

Check for loose connections. Repair of replace heat relay (RH)

Discharge air sensor (TS2) not wired or defective

Wire or replace discharge air sensor (TS2)

Outdoor air sensor (TS1) not wired or defective

Wire or replace outdoor temperature sensor (TS1)

Furnace controller (SC1) defective or not powered

Replace or wire furnace controller (SC1)

Discharge temperature was above high limit control (HLC1)

Wait for high limit to cool and reset

Inlet air sensor contact open

Adjust inlet air sensor setting (refer to 8:1 Staged Start-Up section)

Furnace controller (SC1) defective

Replace furnace controller (SC1)

Airflow switch (PS2) defective

Replace defective airflow switch (PS2)