Troubleshooting
Water Wizard™ — Improper Water Supply
note
If the water supply is too low, the media will continuously appear dry.
note
If the water supply is too high, the media will be saturated and excessive water will be draining from the sump tank.
note
Some water drainage is desired to keep the media flushed, but it should be minimized to utilize the Water Wizard™.
1. Adjust the Manual Supply Valve
Adjust the manual supply valve (refer to
caution
Only proceed to Steps 2 and 3 if Step 1 does not correct the problem.
2. Enter Program Mode
Press and hold the Enter key for
three seconds to enter Program Mode. The display will read “Pro” when Program Mode is active.
3. Adjust the On Time Factor
While in the
Program Menu,
use the Up and Down keys to
navigate through the menu options until “ont” is displayed.
With “ont” displayed, press the Enter key to access the setting.
With the setting displayed, use the Up and Down keys to adjust the setting as needed.
Increase the factor to increase the water supply or decrease the factor to decrease the water supply.
Press the Enter key to save the new On Time Factor and return to the Program Menu.
note
Changing the On Time Factor by (1) will change the water supply by approximately 3%.
important
The Enter key must be pressed to save the new On Time Factor.
4. Exit Program Mode
After 15 seconds of idle time the controller will automatically exit Program Mode.
®
Model IG / IGX