Reference - Model IG

(4:1 Modulation)

 

 

 

 

 

23

25

 

11

 

 

 

 

 

20

21

 

 

 

12 22 24

5

18

 

 

10

 

 

 

 

 

 

26

 

 

 

 

 

 

 

 

18

 

 

 

 

 

 

16

 

 

 

 

 

 

 

 

 

 

 

13

14

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

 

6

 

 

 

 

 

1

7

8

 

 

 

 

 

 

 

 

15

 

 

3

 

 

 

19

 

 

17

2

 

9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

note

This is a typical blower control center, the control center in your unit may be different. Reference the ladder diagram on the inside of the control center door for a unit specific wiring diagram.

1.Supply Motor Starter - 24 volt magnetic contacts for starting supply motor.

2.Supply Overload - Provides electronic overload protection to supply motor.

3.Low Voltage Transformer - Provides low voltage to fan/heat/cooling enable controls, modulating furnace controls and optional evaporative cooling controls.

4.Control Terminal Block - Provides wiring access to controls.

5.Fan Relay - Allows power to pass to energize motor starter.

6.Control Terminal Block - Provides wiring access to fan/heat/cooling enable controls.

7.Auxiliary Contact (Optional) - Provides one normally closed and one normally open contact for other equipment.

8.Exhaust Motor Starter (Optional) - 24 volt magnetic contacts for starting exhaust motor.

9.Exhaust Overload (Optional) - Provides electronic overload protection to exhaust motor.

10.Exhaust Fuses (Optional) - Provides proper fusing for exhaust fan motor(s).

11.Building Freeze Protection Timer (Optional) - Prevents the discharge of cold air into the building.

12.Heat Relay - Allows power to pass to heating controls.

13.Low Voltage Transformer - Provides low voltage to the ignition controller.

14.Heating Terminal Block - Provides wiring access to heating controls.

15.Inlet Air Sensor (Optional) - Outdoor air stat that automatically controls the heating and/or cooling based on outdoor air temperature.

16.Modulation Controller - Provides 4:1 modulating turndown control of the furnace.

17.Amplifier - Controls the modulating valve based on the input from the modulation controller settings and the discharge air sensor.

18.Airflow Switch - Monitors the airflow inside the heat exchanger.

19.Ignition Controller - Controls the ignition of the furnace. Maintains safe operation of the furnace.

20.Modulation Controller (Optional) - Provides proper fusing to modulation controller.

21.Transformer Fuse (Optional) - Provides proper fusing to low voltage transformer.

22.Cooling Relay (Optional) - Allows power to pass to cooling controls.

23.Reset Timer (Optional) - Resets cooling system to run a time interval.

24.Auto Drain Relay (Optional) - Assures supply pump does not operate during drain interval. Allows pump to operate in cooling mode.

25.Cooling Timer (Optional) - Allows for automatic draining of the evaporative cooling system based on time schedule.

26.Dirty Filter Switch (Optional) - Monitors filter pressure drop. Turns on indicating light when pressure drop is above field adjustable set point.

Modulating

Gas Pressure Gas Valve

Test Port

Manifold

 

3/4 inch

 

Gas Supply

 

 

 

Staged

Connection

 

 

 

Gas Valve

 

66 Model IG / IGX Make-Up Air

®

Page 66
Image 66