Greenheck Fan 470656 manual Troubleshooting, 4:1 Modulating Furnace Will Not Light

Models: 470656

1 72
Download 72 pages 41.99 Kb
Page 53
Image 53
Ignition controller(s) (IC#) failed

Troubleshooting

4:1 Modulating Furnace Will Not Light

...continued from previous page

High limit switch (HLC#) open?

No

Ignition controller (IC#)

red LED blinks

7 times or is on

No

Ignition controller (IC#) red LED blinks 6 times

No

24 VAC between terminals

1 and 2 on the Amplifier (AMP)

Yes

10 VDC between terminals

5 and 6 on the Amplifier (AMP)

Yes

24 VDC between terminals

3 and 4 on the Amplifier (AMP)

Yes

Ignition controller (IC#)

red LED blinks

1 time, 2 times or 4 times

No

Everything is working properly,

consult factory.

Yes

Yes

Yes

No

No

No

Yes

Discharge temperature was above high limit setting

Let cool, then reset high limit.

Ignition controller(s) (IC#) failed

Replace faulty ignition controller(s)

Pressure switch (PS2) failure

Repair or replace pressure switch (PS2)

Combustion blower (CM) not functioning

Replace fusing (FU7), combustion blower or relay (CM)

Secondary transformer (TR6) defective

Replace secondary transformer (TR6)

Furnace controller (SC1) defective

Replace furnace controller (SC1)

Amplifier (AMP) defective

Replace amplifier (AMP)

Improper manifold pressure

Set high and low manifold pressure

(refer to 4:1 Electronic Modulation Start-Up section)

Faulty spark rod or spark gap does not equal 1/8 inch

Replace spark rod or adjust gap to 18 inch

®

Model IG / IGX Make-Up Air 53