Honeywell K14114 3/06 Rev.B setup guide Contact Id Event Codes, System Communication, Definition

Models: K14114 3/06 Rev.B

1 72
Download 72 pages 35.87 Kb
Page 58
Image 58
CONTACT ID® EVENT CODES

LYNXR-I Installation and Setup Guide

System Communication

Report

3+1/4+1 Standard

3+1/4+1 Expanded

4+2

 

 

 

 

Alarm

SSS(S) A

SSS(S) A

SSSS AZ

 

 

 

AAA(A) Z

 

Trouble

SSS(S) T

SSS(S) T

SSSS Tt

 

 

 

TTT(T) t

 

Bypass

SSS(S) B

SSS(S) B

SSSS Bb

 

 

 

BBB(B) b

 

AC Loss

SSS(S) E

SSS(S) E

SSSS EAC

 

 

 

EEE(E) AC

 

Low Battery

SSS(S) L

SSS(S) L

SSSS LLB

 

 

 

LLL(L) LB

 

Open

 

SSS(S) O

SSS(S) O

SSSS OU

 

 

 

OOO(O) U

 

Close

 

SSS(S) C

SSS(S) C

SSSS CU

 

 

 

CCC® U

 

Test

 

SSS(S) G

SSS(S) G

SSSS Gg

 

 

 

GGG(G)g

 

Restore Alarm

SSS(S) R

SSS(S) R

SSSS RZ

 

 

 

RRR® Z

 

AC Restore

SSS(S) RA

SSS(S) RA

SSSSRA Ac

 

 

 

RARARA(RA)Ac

 

Low Battery Restore

SSS(S) RL

SSS(S) RL

SSSS RLLB

 

 

 

RLRLRL(RL)LB

 

Trouble Restore

SSS(S) RT

SSS(S) RT

SSSS RTt

 

 

 

RTRTRT (RT)t

 

Bypass Restore

SSS(S) RB

SSS(S) RB

SSSS RBb

 

 

 

RBRBRB (RB)b

 

ADEMCO Contact ID® Reporting takes the following format: CCCC Q EEE GG ZZZ where:

CCCC = Customer (subscriber) ID

 

 

Q

= Event qualifier, where: E = new event, and R = restore

 

EEE= Event code (3 hex digits) (for a complete list of event codes, refer to the central office receiver manual) GG = Always “00”

ZZZ= Zone/Contact ID® number reporting the alarm, or user number for open/close reports. System status messages (AC Loss, Walk Test, etc.) contain zeroes in the ZZZ location.

CONTACT ID® EVENT CODES

Code

Definition

 

 

110

Fire Alarm

121

Duress

122

Alarm, 24-hour Silent

123

Alarm, 24-hour Audible

131

Alarm, Perimeter

132

Alarm, Interior

134

Alarm, Entry/Exit

135

Alarm, Day/Night

146

Silent Burglary

150

Alarm, 24-Hour Auxiliary

301

AC Power

302

Low System Battery/Battery Test Fail

344

RF Jam Detected

353

ECP Communication/Supervision failure, case

 

tamper or low battery

373

Fire Loop Trouble

374

Exit Error Alarm

380

Global Trouble, Trouble Day/Night

Code

Definition

 

 

381

RF Supervision Trouble

383

RF Sensor Tamper (Trouble)

384

RF Sensor Low Battery

401

Disarmed, Armed AWAY (NO DELAY),

 

Armed AWAY

403

Scheduled Auto Arm

406

Cancel by User

407

Remote Arm/Disarm (Downloading)

408

Quick Arm AWAY/NO DELAY

441

Disarmed/Armed STAY/NO DELAY, Quick Arm

 

STAY/NO DELAY

570

Bypass

602

Periodic Test

606

AAV to follow

607

System Test

623

Event Log 80% Full

654

System Inactivity

Notes: (1) The following codes are logged in the event log upon occurrence, but are not reported: 305 = System Reset

627 = Keypad Program Mode Entry

(2)LRR/IP Communications Module Low Battery and Low Battery restore reports are sent real time. LRR/IP Communications Module trouble restore report is sent after two code + off (only if physically restored)

- 58 -

Page 58
Image 58
Honeywell K14114 3/06 Rev.B Contact Id Event Codes, System Communication, LYNXR-IInstallation and Setup Guide, Definition