S y s t e m ( i n c l u d i n g W i r e l e s s )

LYNXR-I Installation and Setup Guide

Troubleshooting Guide

S y s t e m ( i n c l u d i n g W i r e l e s s )

 

SYMPTOM

 

POSSIBLE CAUSE

 

REMEDY

 

 

 

 

 

 

1.

Transmitter signal

1a.

Transmitter not properly powered.

1a

Check or change transmitter's battery.

 

not received at

1b.

Transmitter is located too far from RF

1b.

Move transmitter or RF receiver.

 

control.

 

 

receiver.

 

 

 

 

 

 

 

 

 

1c.

There is metal shielding between

1c.

Check for large metal obstructions, then relocate

 

 

 

transmitter and RF receiver.

 

transmitter if necessary.

 

 

1d.

Transmitter is malfunctioning.

1d.

Verify by activating control with another,

 

 

 

 

 

similar transmitter. If O.K. now, return

 

 

 

 

 

defective transmitter.

 

 

1e.

Transmitter No. (zone) is not

1e.

Verify programming.

 

 

 

programmed.

 

 

 

 

 

 

 

 

2.

Transmitter zone

2a.

Transmitter zone type (ZT) is set to 00

2a.

Set ZT to a valid active zone type in field 56.

 

number appears

 

(Not Used).

 

 

 

during Transmitter

2b.

Transmitter battery not installed.

2b.

Install proper battery.

 

Sniffer mode, but

2c.

5800 System transmitter not "entered" in

2c.

"Enter" unit in field 56 or 83.

 

does not clear.

 

 

system.

 

 

 

 

 

 

 

 

 

 

 

 

 

3.

Low battery message

 

 

 

 

 

on keypad.

 

 

 

 

3a.

"Low Bat" (no zone Nos.)

3a.

System battery is low or missing.

3a.

Replace system battery.

3b.

"Low Bat" + "00".

3b.

Remote RF keypad/button battery is low.

3b.

Replace battery in the RF keypad.

3c.

"Low Bat" + "nn".

3c.

Transmitter for zone “nn” has a low

3c.

Replace the battery in the displayed

 

 

 

battery.

 

transmitter.

 

 

3d.

Standard- or High-Capacity battery

3d.

Ensure that battery is properly connected.

 

 

 

connected to wrong receptacle.

 

 

 

 

 

 

 

 

4.

Periodic beep(s) from

4a.

System is in Test mode.

4a.

Enter Code + OFF to exit Test mode.

 

keypad.

4b.

A transmitter low battery has occurred

4b.

Enter Code + OFF and replace the battery.

 

 

 

and is displayed.

 

 

 

 

4c.

A supervision fault has occurred.

4c.

Check the transmitter indicated. Restore

 

 

 

 

 

communication to the receiver to cancel the

 

 

 

 

 

condition.

 

 

4d.

System low battery

4d.

Replace system battery

 

 

 

 

5. There is no response

Put control in Test mode. If zone does not

 

 

 

to a transmitter in

respond, try operating the tamper switch or

 

 

 

normal operation,

another input to the transmitter.

 

 

 

although zone

5a.

If another input causes the zone to be

5a.

Delete input's serial number (not the zone), and

 

number clears during

 

displayed, the wrong input was "entered"

 

enter the proper input (see field 56).

 

Transmitter Sniffer

 

when programming.

 

 

 

mode.

5b.

If no response at all from this

5b.

Determine which transmitter is programmed for

 

 

 

 

 

transmitter, this physical transmitter

 

this zone and reprogram as necessary.

 

 

 

has not been entered by the system.

 

 

 

 

 

Transmitter Sniffer display is being

 

 

 

 

 

cleared by another unit programmed for

 

 

 

 

 

this zone.

 

 

 

 

 

 

 

 

6.

Nuisance or phantom

6a.

Sensors not properly installed, wired, or

6a.

Check installation to see if in accordance with

 

alarm.

 

monitored.

 

established procedure.

 

 

6b.

Universal transmitter (5817)

6b.

Check programming switches on transmitter.

 

 

 

programmed wrong.

 

 

 

 

 

 

 

 

7.

Intrusion alarm for

7a.

Protected door or window opened while

7a.

Check with all occupants of protected home.

 

no apparent reason.

 

system armed.

 

 

 

 

7b.

Improper user operation of exit/entry

7b.

Check setting of entry and exit delays.

 

 

 

delays.

 

 

 

 

7c.

Magnets located too far from switches,

7c.

Check all openings for proper switch and

 

 

 

and/or doors and windows not properly

 

magnet orientation.

 

 

 

aligned.

 

 

 

 

 

 

 

 

- 60 -