DATAPOINTS | EXCEL 50/100/500/600/800 |
Mapped Datapoints (V2.04.xx or higher)
With firmware version V2.04.xx or higher, those Excel 50/500 controllers which feature free programmability on LONWORKS (those that contain the 3120E5 Neuron chip, i.e. date code 0044 or higher) may have I/O devices connected via the LONWORKS network. LONWORKS network variables (or individual fields of structured network variables) can be mapped to the attribute "Value" of physical datapoints (AI/DI/AO/DO). Pseudo analog, pseudo digital, and pseudo multistage points are also supported for NV mapping.
See Excel 50/500 LONWORKS Mechanisms Interface Description,
12 |