Honeywell R0512 manual System Alarms, Benefits, System alarms

Models: R0512

1 86
Download 86 pages 48.24 Kb
Page 48
Image 48

ALARM HANDLING

EXCEL 50/100/500/600/800

Operational status All datapoints can be switched from the 'automatic' to the 'manual' operational mode. Each time the operating mode is changed, irrespective of the direction involved, a critical alarm signal is generated. Both alarm signal texts are preprogrammed and require no input from the user.

Remote (V2.0.x) (not with Excel 100C) If a manual override control is changed on a Distributed I/O module, an alarm “overr.switch_manu” or “overr.switch_auto” is generated and the “manu” value is transmitted.

Alarm suppression in manual mode Under controller firmware 2.06.02 and higher, the following datapoint alarms can be suppressed for as long as the corresponding datapoints are in the 'manual override' mode:

min. and max. limit alarms (of analog datapoints, only);

status alarms (of digital datapoints, only).

This alarm suppression is activated during CARE engineering by inserting the "at" sign ("@") at the beginning of the descriptor text of the pseudo datapoint "Startup".

Benefits:

As long as this alarm suppression is in effect, the repair or replacement of defective and/or malfunctioning (flickering) inputs (resulting e.g. from sensor breakage, sensor short-circuiting, defective alarm switches, etc.) can be performed while the corresponding datapoint is in the "manual override" mode.

NOTE: Only when using XFI 2.1.0 SIM1 will the event behavior and visualization

behavior be identical to that of Honeywell Deltanet controllers.

System Alarms

 

 

 

Operating errors that occur in a control unit or during communication with other

 

 

 

Excel 50/100/500/600/800 units are recognized and displayed by the computer

 

 

 

module. These alarm signals can relate, for example, to a defective module, the

 

 

 

need to change the buffer battery (data protection), or the presence of one digital

 

 

 

output module too many (maximum 10). These alarm signal texts are

 

 

 

preprogrammed. They are always critical alarms.

 

 

 

Table 20. System alarms

 

 

 

 

Alarm

alarm text

cond.

cause/reason

no.

English)

code #

 

1

AI Module Defect

25

Maximum conversion time was exceeded while testing ADC (defect on an AI card).

 

 

 

 

2

AI 0 Volt Error

24

While measuring GND voltage on an AI card, one value greater than 0.5 V was measured

(AI card defect).

 

 

 

3

AI 5 Volt Failure

23

While measuring the 5-V reference voltage on an AI card, one value greater than 5 V or

smaller than 4.5 V was measured (AI card defect or incorrect power supply of AI card).

 

 

 

4

MAX 2 alarm

2

Alarm limit for AI-, PA points

5

MAX 2 normal

76

Alarm limit for AI-, PA points

 

 

 

 

6

MAX 1 alarm

1

Alarm limit for AI-, PA points

7

MIN 2 alarm

4

Alarm limit for AI-, PA points

8

MIN 2 normal

78

Alarm limit for AI-, PA points

 

 

 

 

9

MIN 1 alarm

3

Alarm limit for AI-, PA points

10

MAX 1 normal

75

Alarm limit for AI-, PA points

11

MIN 1 normal

77

Alarm limit for AI-, PA points

 

 

 

 

 

 

 

1) After starting the Field I/O Task with the parameter "INIT", the default datapoint

12

Alarm memory full

22

description couldn't be installed because USX didn't provide enough storage space for

sending CNAP telegrams.

 

 

 

 

 

 

2) Alarm send buffer full.

 

 

 

 

13

Alarm

6

Alarm condition control for DI , PD points.

EN2B-0092GE51 R0512

46

Page 48
Image 48
Honeywell R0512 manual System Alarms, Benefits, System alarms, Alarm Alarm text Cond Cause/reason English Code #