Honeywell R0512 manual Alarm Handling

Models: R0512

1 86
Download 86 pages 48.24 Kb
Page 49
Image 49

EXCEL 50/100/500/600/800

ALARM HANDLING

 

 

 

 

 

Alarm

alarm text

cond.

cause/reason

no.

English)

code #

 

 

14

Return to normal

79

Alarm condition control for DI, PD points.

15

Hware clock failed

61

Error while initializing the system clock.

 

 

 

 

16

Battery low

17

Battery voltage too low or battery not existent.

17

Battery status OK

87

Battery voltage back to normal again (alarm occurs only after alarm message "Battery

low").

 

 

 

18

Wrong Module ID

71

An invalid module ID is read (error on internal I/O or defect module or the module has an

as-yet unspecified module ID).

 

 

 

19

Too Many DO

60

Too many modules of the same type (XF521, XF522, ...).

Module

 

 

 

 

20

Contr. w/o Flash

81

Error occurred when burning the Flash EPROM.

 

 

 

 

21

FLASH Mem Full

82

Not enough Flash memory space to save application.

 

 

 

 

22

Link Point Alarm

-

Xlink alarm.

23

Link Comm Down

-

Xlink alarm.

24

No characteristic

57

The application part "Characteristics" is defect.

 

 

 

 

 

25

RCL Submod

-

RACL sub-module missing.

missing

 

 

 

 

26

Download SSI Now

-

Xlink alarm.

27

Download CPU

-

Xlink alarm.

Now

 

 

 

 

28

RACL inconsistent

29

Incompatible version numbers of RACL program and RACL parameter files and/or

datapoint description.

 

 

 

29

Nested

30

RACL program contains errors (MCAL from submodule).

submodules!

 

 

 

 

30

alarm message

-

Alarm not used.

158

 

 

 

 

31

RACL undef.

32

RACL program contains errors (undefined Operation code).

OpCode

 

 

 

 

32

RACL program

33

RACL program contains errors (Checksum changed).

fault

 

 

 

 

 

 

 

1) During RACL run, datapoint contains errors or point is locked.

33

Unknown datapoint

34

2) An unrecognized (missing) characteristic in the datapoint editor has been used.

 

 

 

Check if the default file set of the controller is different from the set used in CARE.

34

SSI Points Active

 

Xlink alarm.

 

 

 

 

35

Invalid operation

36

Non-valid arithmetical operation during RACL performance (e.g. division by zero or RACL

statements LN with input value 1.0 ).

 

 

 

36

RACL overflow

37

Arithmetic overflow at RACL performance "+infinite".

37

RACL neg.

38

Arithmetic underflow at RACL performance "-infinite".

overflow

 

 

 

 

38

RACL inval.

39

RACL program contains errors (invalid Operation Code).

OpCode

 

 

 

 

39

Z-Reg. index error

40

Access to non-existing Z register (e.g.: RACL statements ISTO and IRCL).

40

Invalid Y-Register

41

Too many statements (exits) in one column.

 

 

 

 

41

Invalid P-Register

42

Attempt to use non-existent P register.

42

Invalid T-Register

43

Attempt to use non-existent T register.

43

Invalid Z-Register

44

Attempt to use non-existent Z register.

 

 

 

 

44

SSI Interface Up

-

Xlink alarm.

45

No parameter file

-

RACL parameter file missing.

46

No Z file

-

RACL Z register file missing.

 

 

 

 

47

No T file

-

RACL time register file missing.

47

EN2B-0092GE51 R0512

Page 49
Image 49
Honeywell R0512 manual Alarm Handling