ATTRIBUTES

EXCEL 50/100/500/600/800

VALUE

TREND

VALUE

TREND

VALUE

TREND

VALUE

TREND CYCLE TREND CYCLE

TIME

Fig. 22. The attribute "Trend Cycle"

The value of the attribute "Trend Cycle" is given in minutes, and the valid range is 0 to 1440 min (=24 hours). A trend cycle value of 0 will disable time-based trending (this is the default) and value-hysteresis trending is used if the trend log attribute is set. The value for the attribute "Trend Cycle" can be changed via the MMI, C-Bus, or modem connection to EBI/SymmetrE, and also via CARE RIA/WIA statements.

NOTE If the attribute "Trend Cycle" is set to anything other than 0, trending will be time-based and the attribute "Trend Hysteresis" will be ignored.

 

 

 

User Address

 

 

 

 

 

 

The attribute "User Address" is a sequence of up to 18 letters and numbers

 

assigned to each datapoint (physical and pseudo).

Example

The temperature of a room is recorded at a sensor input; the associated user

 

address could be as follows:

 

Room Temp.1.10

(Room temperature, 1st floor, room 10)

 

The datapoint can be accessed directly by selecting this user address on the XI581

 

(not with XCL5010, Excel 100C), XI582, and XL-Online operator interfaces or the

 

XL50-MMI.

 

 

 

In the case of basic types of physical data, a user address always corresponds

 

exactly to one technical address (see Table 15).

 

The user address of flexible datapoints may refer to up to six technical addresses.

 

 

Table 15. Number of technical addresses for flexible datapoints

 

 

 

 

 

 

 

flexible datapoint

number of technical addresses

 

 

 

Pulse 2

2

 

 

 

Multi-stage

up to 6

 

 

 

 

 

 

 

 

Feedback

up to 6 (in pairs of 2)

 

Value

When the controller is working in automatic (the attribute "Operating Mode" is set to "Auto"), the value currently being processed by the program, or the current status, can be found in the attribute "Value". The attribute "Value" for an analog input could contain, for example, the current room temperature of 21 °C / 70 °F.

A pump switched by a digital output could contain the current status of the pump, for example ON, in its attribute "Value".

EN2B-0092GE51 R0512

36

Page 38
Image 38