Honeywell R0512 manual Warm Start

Models: R0512

1 86
Download 86 pages 48.24 Kb
Page 50
Image 50

ALARM HANDLING

 

 

EXCEL 50/100/500/600/800

 

 

 

 

 

 

Alarm

alarm text

cond.

cause/reason

 

no.

English)

code #

 

 

 

 

 

46

1)

No RACL program.

 

48

Part applic. miss

47

2)

No parameter file.

 

48

3)

No Z register file.

 

 

 

49

4)

No T register file.

 

 

 

52

5)

No datapoint description.

 

 

 

26

1)

Submodule does not exist.

 

 

 

27

2)

Parameter file missing.

 

 

 

28

3)

No M0 module.

 

49

RACL environ fault 31

4) Invalid SKIP destination.

345) Info points STARTUP, SHUTDOWN, or EXECUTING_STOPPED are missing or

6) During RACL start datapoint contains errors.

1

7) freely programmable application loaded into Excel 50 controller (system alarm

parameters set to 0,0,0).

 

50

INIT div. by zero

14

Reason of new start: Division by zero.

51

INIT under OpCode

15

Reason of new start: the system software contains an undefined Operation Code.

52

Power failure

16

Reason of new start: power failure, data in RAM ok.

 

 

 

 

53

Link Config Bad

-

Xlink alarm.

54

I/O board missing

19

The required configuration contains at least one module which is not included in the

hardware configuration.

 

 

 

55

Unused I/O board

18

The hardware configuration contains at least one module that is not needed (can be taken

out).

 

 

 

 

 

 

1) Hardware Configuration file (.kfx file) not complete loaded.

 

 

 

2) Different modules are plugged under the same address (set using the rotary HEX

56

HW Config. failure

20

switch) in the required configuration and in the hardware configuration.

 

 

 

3) An application containing NV-mapping is rejected by the target controller because the

 

 

 

hardware does not have the 3120E5 Neuron® chip.

57

Wrong version no.

21

The version number of the application files and the configuration file are not the same.

 

 

 

 

58

Totalizer overflow

5

Overflow operation hours counter, point value of counters and interval impulse counter.

59

Maintenance alarm

7

Course of a service interval for digital points or course or the message/calling interval for

counters. Call intervals for counters.

 

 

 

60

Undef. RACL input

62

Undefined RACL errors.

 

 

 

The loaded application contains too many remote points. An application with more than 46

61

Too many Globals

63

NVs has been rejected for download into an Excel 50 freely programmable controller

 

 

 

located on a LONWORKS network.

62

C-Bus error

64

Communication defect/disturbance between Excel 500 and C-Bus submodule. Logical

modem device in controller has gotten a C-Bus # already in use for a C-Bus controller.

 

 

 

63

No Globals

9

No remote storage; the remote controller has no storage left for requested remote points.

memory

 

 

 

64

Global pnt missing

10

The user address of the remote point was not found in the remote controller.

 

 

 

 

65

Glob Pnt Occupied

11

A remote output to a remote controller is already assigned to another controller.

66

CPU stopped

12

The remote controller is in stopped condition.

67

CPU not available

13

The remote controller is switched off or does not respond to C-Bus communication.

 

 

 

 

68

Init. actuators

65

Floating outputs (3-position outputs) are synchronized.

69

WARM START

66

Reason of new start: watchdog.

70

COLD START

67

Reason of new start: power failure, data in RAM destroyed.

 

 

 

 

71

Point in manual

68

When falling back to password level 3 there are still points in manual override.

 

 

 

 

72

Report too large

69

Not enough space in the report file for initialization.

73

XI 581 required

70

After a download, an entry is demanded in the initializing phase of the ASPECD

application. This can happen only with XI581 emulation.

 

 

 

74

New appli. loaded

74

Download of a new application part or entire application.

 

 

 

 

EN2B-0092GE51 R0512

48

Page 50
Image 50
Honeywell R0512 manual Warm Start