Honeywell R0512 manual Active State prior to, Active State Excel, Status text

Models: R0512

1 86
Download 86 pages 48.24 Kb
Page 16
Image 16

ATTRIBUTES

EXCEL 50/100/500/600/800

Active State (prior to V2.04.x)

The attribute "Active State" defines when a digital input/output is active.

NOTE: The "Active State" attribute does not reflect the current condition of a digital datapoint.

NOTE: This is not applicable to digital inputs in applications designed for con- trollers using V2.04.xx firmware or higher. In such applications, this attribute is fixed at 1, and the new attribute "Normally Open/Normally Closed" (NO/NC) is active (see section "Normally Open/Normally Closed (V2.04.xx or higher)" on page 28 for more details).

The following values are possible:

0 = digital input/output is active when a "logical 0 signal" is present

1 = digital input/output is active when a "logical 1 signal" is present

Table 3 indicates the active state for various conditions of the XF523 and XFL523 modules.

Table 3. Active state for the digital input of XF523 and XFL523 modules

 

 

 

 

 

 

digital input

 

 

 

 

contact status

 

 

open

 

 

 

 

closed

 

CARE definition

 

NC

 

NO

NC

 

NO

 

(NC/NO system diagram)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

definition - in XL-Online DP-

 

 

 

 

 

 

 

 

 

 

 

 

Editor attribute "Active State"

1

 

0

1

 

0

1

 

0

1

 

0

(change Active/Passive State

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

text)

 

 

 

 

 

 

 

 

 

 

 

 

CARE interpretation

1

 

1

0

 

0

0

 

0

1

 

1

(control table)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

display at operator interface

OFF/

 

ON/

OFF/

 

ON/

ON/

 

OFF/

ON/

 

OFF/

trouble:

 

operating

trouble:

 

operating

operating

 

trouble:

operating

 

trouble:

(status text)

 

 

 

 

 

alarm

 

RTN*

alarm

 

RTN*

RTN*

 

alarm

RTN*

 

alarm

 

*

RTN = Return

To Normal

 

 

 

 

 

 

 

 

NOTE: XFL523 Module is applicable only for V2.0.xx software.

 

Active State (Excel 800)

The attribute "Active State" defines when a digital input/output is active. 1 means, that a digital input/output is active when a "logical 1 signal" is present

NOTE: "Active State" = 0 is not allowed/possible.

NOTE: The "Active State" attribute does not reflect the current condition of a digital datapoint.

Table 4. Active State for the digital input of XF823 and XFL823 modules

 

 

 

 

 

 

digital input

 

 

 

contact status

 

 

open

 

 

 

closed

CARE definition

NC

 

NO

 

NC

 

NO

(NC/NO system diagram)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

definition - in XL-Online DP-

 

 

 

 

 

 

 

 

 

 

 

Editor attribute "Active State"

1

 

 

1

 

 

1

 

 

1

 

(change Active/Passive State

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

text)

 

 

 

 

 

 

 

 

 

 

 

EN2B-0092GE51 R0512