EXCEL 50/100/500/600/800

ATTRIBUTES

Motor Run Time

Time to open / time to close For actuators controlled via a three-position output, two values (time to open / time to close) can be entered in the attribute “Motor Run Time”. This attribute defines the time required by the actuator to change from the “Open” to the “Closed” state, and vice versa.

If no value is entered for the “Time to Closed” motor run time, then the “Time to Open” motor run time is assumed automatically. In the case of the motor run-on time, when reversing directions, 1% of the “Time to Open” motor run time is added to the calculated time.

The three-position output relay energizes when the calculated run time reaches 500 ms. The stated run time always amounts to 500 ms or a multiple thereof. A calculated run time of, for instance, 1215 ms results in an actual run time of 1000 ms.

CAUTION

Regarding motor run time, the behavior of controllers with OS < 2.06.05 engineered using CARE 4 differs significantly from controllers with OS

2.06.05and higher engineered using CARE 7 and higher. See also section “Controller OS 2.06 usage and functionality in CARE 4 and CARE – XL500 7.01.02” in Excel CARE – User Guide (EN2B-0182GE51).

Off Phase

Fig. 16. Off phase

The attribute "Off Phase" is used in conjunction with flexible datapoints of the type "feedback". It defines the duration of the OFF phase on switching down. It is of relevance only if the attribute “Switching Down” is set to 0, i.e. if OFF phases are selected on switching down.

Range:

0 to 255s

Default value: 10s

Resolution: 1s

The OFF phase has to be defined for devices with large inertia, such as fans.

Operating Mode

The attribute "Operating Mode" enables the user to switch between manual and automatic operation.

Automatic Under automatic operation, the controller processes the values at the inputs, for instance from temperature sensors. For outputs, under automatic operation, the status shown by the user/time switch program is adopted, e.g., "Heating circuit pump off".