ATTRIBUTES

 

 

 

 

 

EXCEL 50/100/500/600/800

 

 

 

 

 

 

 

 

 

alarm type/attributes

alarm status

 

enter alarm

alarm

point in

no. of prepro-

supplementary

 

 

delay time

suppression

alarm

grammed texts

text

 

 

 

 

 

user program reports

always non-critical

-

-

-

-

-

 

*DPD = datapoint description

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE: A point is still seen as “in alarm” even when alarm suppression is

 

 

 

enabled.

 

 

 

 

Cycle Count

The attribute "Cycle Count" contains the value indicating the number of transitions to the active state (see "Active State (prior to V2.04.x)" on page 14).

Delay Time Switching Up

This attribute is used in conjunction with flexible points of the type "feedback". It defines the delay time between switching upwards from one stage to another. The delay time affects every stage. The delay time also takes effect when switching, e.g. from manual value 0 to 2. In this case, it is switched from stage 0 to stage 1, then to stage 2 with the delay time between the switching processes.

Range:

0 to 255s

Default value:

10s

Resolution:

1s

Fig. 8. Delay time switching up

Delay Time Switching Down

This attribute is used in conjunction with flexible points of the type "feedback". It defines the delay time between switching downwards from one stage to another. The delay time affects every stage.

Range:

0 to 255s

Default value:

10s

Resolution:

1s

The feedback delay time starts to count after termination of delay time switching up/delay time switching down.